4.3 Time Overcurrent Protection
269
7ST6 Manual
E50417-G1176-C251-A3
Tolerances
Characteristics and Graphics
Trip Time Characteristics IEC
DT
Currents
5 % of setting value for I
Act
≥
I
N
Times
1 % of setting value, at least 10 ms
With high-speed overcurrent protec-
tion
1 % of setting value, at least 3 ms
IDMT
Pickup/dropout thresholds
I
p
,
I
Ep
2 % of set value or 10 mA for
I
N
= 1 A
or 50 mA for
I
N
5 A
Pickup time for 2
≤
I
/
I
p
≤
20
5 % of reference (calculated) value +2 % current tolerance, or
30 ms