2.2 Distance Protection
65
7ST6 Manual
E50417-G1176-C251-A3
Independent Zones
The table below shows the assignment of the general characteristic parameters to the
concrete setting values for the independent zones:
Table 2-2
Assignment of setting parameters for the independent zones of the distance
protection
In each zone, different values for reach and minimum load impedance can be set in
forward and reverse direction.
The setting parameters marked with „reverse“ (e.g.
Z1 Reverse
) are only visible if
you have set „
non-directional
“ for the distance stage of the corresponding zone.
Dependent Zones
These parameters are only available in combination with the auto reclose function, i.e.
if you have set address
133
Auto Reclose
to
Enabled
during the configuration of
the functional scope.
For tripping within the first AR cycle, zone Z1B instead of zone Z1 is used. For the
second and the following cycles, zone Z1L is used. Zone Z1 is activated if the AR func-
tion is blocked, or in the last cycle of the AR.
The impedance characteristics for the AR zones Z1B and Z1L must have the same
characteristic type (combined, polygonal) and the same angle parameters (
α
,
β
,
γ
) as
zone Z1. Therefore, these parameters cannot be set for the AR zones. They are nor-
DIGSI® set-
ting sheet
Parameter
Setting parameters
Z active
Z Strk active
Zone Z1
Z, X, R
L
Z1 (Addr.1310)
X1 (Addr.1309)
R1 (Addr.1308)
Z1 Reverse (Addr.1316)
X1 Reverse (Addr.1315)
R1 Reverse (Addr.1314)
Z1 Strk (Addr.1318)
X1 Strk (Addr.1317)
R1 Strk (Addr.1207)
Z1 Strk Reverse (Addr.1320)
X1 Strk Reverse (Addr.1319)
R1 Strk Reverse (Addr.1208)
Mode
Op. Mode Z1 (Addr.1301)
Alpha
ALPHA Z1 (Addr.1311)
Beta
BETA Z1 (Addr.1312)
Gamma
GAMMA Z1 (Addr.1313)
Zone Z2
Z, X, R
L
Z2 (Addr.1350)
X2 (Addr.1349)
R2 (Addr.1348)
Z2 Reverse (Addr.1356)
X2 Reverse (Addr.1355)
R2 Reverse (Addr.1354)
Z2 Strk (Addr.1358)
X2 Strk (Addr.1357)
R2 Strk (Addr.1217)
Z2 Strk Reverse (Addr.1360)
X2 Strk Reverse (Addr.1359)
R2 Strk Reverse (Addr.1218)
Mode
Op. Mode Z2 (Addr.1341)
Alpha
ALPHA Z2 (Addr.1351)
Beta
BETA Z2 (Addr.1352)
Gamma
GAMMA Z2 (Addr.1353)
Zone Z3
Z, X, R
L
Z3 (Addr. 1370)
X3 ( Addr.1369)
R3 (Addr.1368)
Z3 Reverse (Addr.1376)
X3 Reverse (Addr.1375)
R3 Reverse (Addr.1374)
Z3 Strk ( Addr.1378)
X3 Strk (Addr.1377)
R3 Strk (Addr.1227)
Z3 Strk Reverse (address 1380)
X3 Strk Reverse (Addr.1379)
R3 Strk Reverse (Addr.1228)
Mode
Op. Mode Z3 (Addr.1361)
Alpha
ALPHA Z3 (Addr.1371)
Beta
BETA Z3 (Addr.1372)
Gamma
GAMMA Z3 (Addr.1373)