9 Operation at Use of a PC
9.7 Example of a Parameterization and Measured Value Evaluation
332
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
✧
On the
Configure
tab,
Device and language
menu item assign a device name and the format for the date
and time display on the HTML pages as described in chapter 9.3.7.7.
Figure 9-147
Configure Tab, Device and Language Example
✧
On the
Configure
tab,
Recorder management
menu item (see chapter 9.3.6.3), configure the
Measurement recorder
with an averaging time of 2 hours and the recorders of average to record all
voltage harmonics.
Figure 9-148
Configure Tab, Recorder Management Example