9 Operation at Use of a PC
9.3 Configuration of the Device
169
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.3.1.3
Binary Outputs G1/G2 and G3/G2
Default Settings and Setting Ranges of the Binary Outputs G1/G2 and G3/G2
Table 9-4
Settings of Binary Outputs G1/G2 and G3/G2
Parameter
Default Setting
Setting Range
Source type
Indication
Indication
Energy counter
Source Type Indication
Indication
-none-
Acc. to list box
(see chapter 16)
Source inverted
no
no
yes
Operating mode
Persistent
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating mode
(setting only possible if operating
modes
Pulse
and
Pulse with retrig-
ger
)
20 (* 10 ms)
50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter
-none-
Acc. to list box
(see chapter 16)
Energy increase per pulse
1.0 Wh
0.1 Wh/VAh/varh to 1 000 000 Wh/VAh/
varh
Output time for pulse operating mode
20 (* 10 ms)
50 ms to 3 600 000 ms