9 Operation at Use of a PC
9.7 Example of a Parameterization and Measured Value Evaluation
329
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.7.3
Parameterization as Defined by the Task
Requirements
SICAM Q100 is electrically connected to the system and commissioned as described in chapter 7.7. Rated
voltages and currents at the measuring inputs are switched off.
Parameterization
✧
Start the user interface as described in chapter 9.2.1 (initial startup) or chapter 9.2.7 (start during
operation). Use the factory-preset IP address for this purpose.
✧
On the
Configure
tab, configure the element
AC measurement
(see chapter 9.3.3.1.1) according to the
following topology specifications:
Figure 9-142
Configure Tab, AC Measurement Example
NOTE
If you change settings in tabs, click
Send
on each tab to confirm the new setting. The settings are
activated
only after the entire parameterization has been completed.
NOTE
If you are using Ethernet communication with
IEC 61850 bus protocol
(chapter 9.3.7.2) and change the
Network type
, the device will restart.