9 Operation at Use of a PC
9.3 Configuration of the Device
202
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Recording with the Trend Recorder
The recording of data points (voltage values with a time stamp) that have exceeded/fallen below the parame-
terized
tolerance value
(fault) and the associated creation of a PQDIF file is determined by 2 trigger criteria:
•
Creation of a PQDIF file after the parameterized
Maximum recording interval
(for example, 24 h) has
been reached if within this interval no 1024 data points have been generated yet.
•
Creating a PQDIF file without considering the parameterized
Maximum recording interval,
if the voltage
has exceeded/fallen below the tolerance range 1024 times and therefore 1024 data points have been gen-
erated.
Figure 9-50
Trend Recorder, Function When the 24 h Interval Is Set
0:00
24:00
16:00
08:00
Data points
1024 / 0
1024 / 0
PQDIF file
recording
0
04:00
12:00
20:00
06:50
Recording time
18:45
Recording
all 1024 data points
Clock time
Start time
120 / 0
Recording
120 data points
Recording
all 1024 data points
1024 / 0
Recording all
1024 data points
14:15
NOTE
A data point is created when the voltage exceeds or falls below the parameterized tolerance value. The data
point represents this voltage value in the PQDIF file.
MAN_SICAM_Q100_US.book Page 202 Wednesday, June 5, 2019 9:31 AM