9 Operation at Use of a PC
9.5 Maintenance
304
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.5.1
Firmware Upload
During a firmware update, the device firmware, the default set of parameters, text libraries, HTML files or parts
thereof are updated.
9.5.1.1 Firmware Upload via User Interface
To update the firmware in the
Maintenance
tab, proceed as follows:
✧
Select
Firmware upload
in the navigation window.
Figure 9-119
Maintenance Tab, Firmware Upload - Enable Upload Input/Output Window
✧
Click
Enable upload
.
NOTE
Before updating the firmware, Siemens recommends saving the current parameters set as described in section
Activating the Set of Parameters
NOTE
If you have activated the option in your web browser to transfer the local directory name together with the file
name when uploading files, then the total number of characters in the directory and file names may not exceed
100 English characters. Otherwise, the firmware in your device will not be updated.
NOTE
Do not switch off the supply voltage during the firmware upload process.
If you want to carry out a firmware update, you must stop the recording before manually.