16 Operating Parameters
16.6 Administrative
426
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6.5
Modbus Slave Devices 1 – 8
16.6.5.1 Basic Settings
Parameter
Default Setting
Setting Range
Name
Modbus slave device 1
Max. 31 characters
Activated
no
no
yes (= Activation of the option field):
The buttons for parameterization of the
mapping data are also activated for the
slave device here.
Device address / Unit ID
(Modbus slave device address)
1
1 to 247
Address corresponds to the Unit ID in
the Modbus TCP telegram with simulta-
neous use of the Modbus Gateway func-
tion.
Response timeout
10 (*10 ms)
1 to 6000 * 10 ms
(10 ms to 60 s)
Retry limit
2
0 to 10
(0 = no request retries)
Number of request retries after expira-
tion of
Response timeout
before a com-
munication error for the Modbus slave is
identified.
Scan cycle for measured values
50 (*10 ms)
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = each request cycle
Minimum time difference between the
measured-value requests.
Scan cycle for indications
0 (*10 ms)
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = each request cycle
Minimum time difference between the
measured-value requests.
Scan cycle on error
5 s
1 to 3600 s
( 1 s to 1 h)
Retry cycle for sending request tele-
grams if the retry limits are exceeded or
in the case of error responses.