9 Operation at Use of a PC
9.3 Configuration of the Device
239
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.7.5 Modbus Slave Devices 1-8
For the correct functioning of the Modbus RTU Master, the Modbus RTU Master must know all Modbus slave
devices which are connected to the RS485 interface and the data which the devices must read must have been
defined. See also System Manual SICAM Q100, chapter 2.
You can parameterize up to 8 Modbus slave devices. They can be selected in the 2 groups
Modbus slave
devices 1-4
and
Modbus slave devices 5-8
. The parameterization of the 8 Modbus slave devices is identical
and described only for the Modbus slave device 1 in the following.
9.3.7.5.1
Basic Settings
Default Settings and Setting Ranges of the Modbus Slave Device 1
NOTE
Modbus slave devices can only be parameterized if you selected the communication protocol Modbus RTU
Master.
NOTE
The parameterization sequences for the Modbus RTU Master and the Modbus Gateway are described in detail
in chapter 9.8.
Table 9-32
Settings of the Modbus slave device 1
Parameter
Default Setting
Setting Range
Name
Modbus slave device 1
Max. 31 characters
Activated
no
no
yes (= Activation of the option field):
The buttons for parameterization of the
mapping data are also activated for the
slave device here.
Device address/Unit ID
(Modbus slave device address)
1
1 to 247
Address corresponds to the Unit ID
in the Modbus TCP telegram with simul-
taneous use of the Modbus Gateway
function.
Response timeout
10 (*10 ms)
1 to 6000 * 10 ms
(10 ms to 60 s)
Retry limit
2
0 to 10
(0 = no request retries)
Number of request retries after expira-
tion of
Response timeout
before a com-
munication error for the Modbus slave is
identified.