9 Operation at Use of a PC
9.3 Configuration of the Device
185
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
✧
In the navigation window of the
Energy management
menu click
Load profile
.
Figure 9-40
Configure Tab, Load Profile Input/Output Window
✧
Select the respective parameters in the list boxes according to Table 9-10.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
NOTE
Changing the number and length of the subperiods deletes the load-profile buffer.
NOTE
If a binary input is used as synchronization source its properties must be configured (see chapter 9.3.3.1.2
Con-
figure
->
Operational parameters
->
Process connections
->
Binary inputs
).