16 Operating Parameters
16.5 Recording and Reporting
412
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5
Recording and Reporting
16.5.1
Event Recorders
1)
According to IEC61000-4-30 Ed.3, RVC hysteresis is recommended to be half of the threshold.
2)
RVC event detection mode
will always synchronize with the setting
Event detection mode
.
Parameter
Default Setting
Setting Range
Voltage event
Swell threshold
110 %
105 % to 140 % in 5-% steps
Dip threshold
90 %
75 % to 95 % in 5-% steps
Interruption threshold
5 %
1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis
2 %
1 % to 6 % in 1-% steps
Event detection mode
ph-N
ph-N
ph-ph
RVC event
RVC threshold
6 %
1 % to 6 % in 1-% steps
RVC hysteresis
1)
3 %
0.5 % to 3 % in 0.5 steps
RVC event detection mode
2)
ph-N
ph-N
ph-ph
Frequency event
Underfrequency threshold
1 %
0.1 % to 1.0 % in 0.1-% steps and
1.0 % to 5.0 % in 1.0-%-steps
Overfrequency threshold
1 %
0.1 % to 1.0 % in 0.1-% steps and
1.0 % to 5.0 % in 1.0-%-steps
Voltage-unbalance event
Voltage-unbalance threshold
5 %
1 % to 5 % in 1-% steps
MAN_SICAM_Q100_US.book Page 412 Wednesday, June 5, 2019 9:31 AM