16 Operating Parameters
16.6 Administrative
421
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6.2
Ethernet Communication
Parameter
Default Setting
Setting Range
Communication Ethernet
IP address
1)
192.168.0.55
Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Ethernet switch on
no
no
yes
Enable SNMP
no
no
yes
OPC UA PubSub (MQTT)
no
no
yes
Bus protocol
Modbus TCP
-none-
Modbus TCP
IEC 61850
Both
Protocol Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10 000
10 000 to 65 535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 (* 100 ms)
0 s = none
100 ms to 6 553 400 ms
Modbus TCP/RTU Gateway
(Condition: The Modbus RTU Master protocol must have been selected under serial communication.)
Activated
no
no
yes