9 Operation at Use of a PC
9.3 Configuration of the Device
258
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Checking Additional Settings in the SICAM I/O Unit Subdevice
Binary Inputs
✧
Check the
Threshold voltage
and
Software filter time
settings of the binary inputs:
Figure 9-81
Binary Inputs of SICAM I/O Unit
✧
Check the time synchronization settings and select preferably
Ethernet NTP
as the source of time
synchronization, if available.
Communication indication
If data are exchanged correctly between SICAM Q100 and the SICAM I/O Unit, the indication
I/O Mirror server
OK
is set to
ON
in the SICAM I/O Unit.