9 Operation at Use of a PC
9.3 Configuration of the Device
218
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Settings Protocol Modbus
✧
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 9-24.
Figure 9-58
Protocol Modbus
Settings Modbus TCP/RTU Gateway
To active
Modbus TCP/RTU Gateway
, proceed as follows:
✧
Select
yes
in
Administrative
->
Communication Ethernet
->
Modbus TCP/RTU Gateway
->
Activated
.
Figure 9-59
Modbus TCP/RTU Gateway
✧
Enter the desired values into the fields (acc. to Table 9-24).
✧
After the parameterization click
Send
.
After clicking
Send
, the parameters are transmitted to the device but not enabled yet (passive set of
NOTE
If you have selected
no
under
Use a user-port number
, you can adjust only the
Access rights for user
port 502
, the
Keep Alive time
and the
Communication supervision time
parameters.
NOTE
The Modbus TCP/RTU Gateway function requires that the Modbus RTU Master has been selected as serial
protocol in addition; see chapter 9.3.7.3.