9 Operation at Use of a PC
9.3 Configuration of the Device
209
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Changing the Report Configuration
To change the report configuration, proceed as follows:
✧
In the navigation window of the
Recording and Reporting
menu click
Report configuration
.
Figure 9-53
Configure Tab, Report Configuration Input/Output Window (Excerpt)
✧
Use the buttons to select the evaluation mode or enter the user-defined mode into the fields according to
Table 9-20.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
according to section
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
NOTE
The chapter 9.4.2.4 describes the output of the power quality report.