13 Failures and LED Indications
13.2 Indications Signaled by LEDs
371
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Table 13-1
Indications Signaled by LEDs on the Top Side of the Housing
LED
Meaning
No Operation
Device is switched off.
Device is switched on, but firmware is not loaded.
or
Device is in startup phase.
Normal Operation
Configured IP address is used.
or
IP address is received via DHCP.
H1
and
H2
LEDs are configured.
Normal operation with default IP address
The default IP address was requested by pressing the F4 softkey during
normal operation.
Double IP address has been detected in the network.
The device is in operation but cannot be reached via Ethernet.
Solve this network configuration issue and restart the device.
Each device must have a unique IP address.
An IP address request via DHCP is in progress.
ERROR
= off, H1 and H2 LEDs according to configuration
RUN
LED stops flashing when IP address is received.
The device runs into the Fallback mode after an unresolvable error in normal
operation occurs or by pressing the
F4
softkey during device startup.
RUN
ERROR
H1
H2
RUN
ERROR
H1
H2
RUN
ERROR
H1
H2
C
C
RUN
ERROR
H1
H2
C
C
ERROR
RUN
H1
H2
C
C
ERROR
ERROR
RUN
H1
H2
C
C
ERROR
MAN_SICAM_Q100_US.book Page 371 Wednesday, June 5, 2019 9:31 AM