9 Operation at Use of a PC
9.3 Configuration of the Device
203
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.4 Mains Signaling Voltage
Default Settings and Setting Ranges
Changing the Mains Signaling Voltage Parameters
To change the
Mains signaling voltage
, proceed as follows:
✧
In the navigation window, select the
Recording and Reporting
menu and click
Mains signaling voltage
.
Table 9-18
Mains Signaling Voltage
Parameter
Default Setting
Setting Range
Mains signaling voltage measurement
MSV active
no
no
yes
No. of MSV frequencies
1 frequency
1 frequency
2 frequencies
Frequency 1
216.60 Hz
100 Hz to 3 kHz
Frequency 2
1060.00 Hz
100 Hz to 3 kHz
Mains signaling voltage capture setting
Detection threshold
1 [% of Udin]
1 % to 15 % of Udin
Total recording duration
75 s
15 s to 120 s in 15-s steps
Pretrigger ratio
10 %
0 % to 30 % in 5-% steps