9 Operation at Use of a PC
9.3 Configuration of the Device
197
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.3 Recorder Parameter
Default Settings and Setting Ranges
Table 9-16Recorder Parameter
Parameter
Default Setting
Setting Range
Measurement Recorder
PQ data Parameter
Average intervals - Frequency
10 s
fixed
Short-term flicker
10 min
fixed
Long-term flicker
2 h
fixed
Average interval - Voltage,
Unbalance and Harmonics
10 min
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no
no
yes
Recorder of average - Min
no
no
yes
Recorder of average - Max
no
no
yes
Harmonics parity
Odd
Even
Odd
All
File generation every:
1)
(corresponds to the setting of
the
Average interval
parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h
At average interval
File generation
every:
30 s
1 h (fix)
1 min
2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type
PQDIF
PQDIF (see chapter 9.4.2.5)
CSV
All
Flicker lamp model
230 V
230 V
120 V
Energy value Parameter
Energy value recorder
10 minutes
Not configurable
The same as the value of
Interval
set in
Configure
->
Energy management
->
Energy freeze and reset
.
Trend Recorder