HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.4.17
NAMUR status signal
Select one or more NAMUR sta‐
tus signals. The output is active
when one of the selected signals
occurs.
● Failure
● Function
check
● Out of
specification
● Maintenance
required
● None
User
2.4.4.18
Polarity
Set the level of an active signal. Active high level ● Active high
level
● Active low
level
User
2.4.4.19
On delay
Set the time delay between
alarm condition and activating
the output. Allows to ignore tran‐
sient fault conditions
0 s
● 0 to 100 s
User
2.4.4.20
Off delay
Set the time delay between re‐
setting alarm condition and de-
activating the output. Allows to
ignore transient fault conditions
0 s
● 0 to 100 s
User
1)
: See Sensor dimension dependent default settings (Page 259)
Table B-14
Channel 4 – input/output
HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.5.1
Operation Mode
Set the output functionality you
want the channel to operate.
Off
● Off
● Current output
● Frequency
output
● Pulse output
● Digital output
● Digital input
User
2.4.5.2
Change operation mode
2.4.5.3
Active operation
Shows the application possibili‐
ties of your hardware. The kind
of operation depends on the wir‐
ing.
● Active
operation not
possible
● Active
operation
possible
User
2.4.5.4
Fail-safe activation con‐
dition
Fail-safe becomes active if ei‐
ther the selected process value
is unreliable, or the device
shows "Maintenance alarm".
Invalid process
value
● Invalid
process value
● Maintenance
alarm
User
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA