MASS 2100
ATEX Certificate : DEMKO 03 ATEX 135252X
Sitrans FC MASS 2100 can be used in zone 0, 20
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
IECEx Certificate : IECEx ULD 17.0029
Sitrans FC MASS 2100 can be used in zone 0, 20
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
Canada Certificate. UL E232147
Sitrans FC MASS 2100 can be used in zone 0, 20 and Class I+II+III Division 1. Grp. A,B,C,D,
E, F, G
Class I+II+III Division 1. Grp. A,B,C,D, E, F, G.
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C…T180°C Da
US Certifikate: UL E232147
Sitrans FC MASS 2100 can be used in zone 0 and Class I Division 1.
Class I+II+III Division 1. Grp. A,B,C,D, E, F, G.
AEx ia IIC T6…T3 Ga
AEx ia IIIC T135°C…T180°C Da
2.4.5
Special conditions for safe use
Special conditions for safe use
In general, it is required that:
● The transmitter electronic compartment shall not be opened when energized and when an
explosive gas or dust atmosphere may be present.
● The terminal compartment may be opened when an explosive gas or dust atmosphere may
be present at any time. Access power terminals by lifting the cover only when de-energized.
● Appropriate cable connectors are used.
● Substitution of components may impair Intrinsic Safety.
Safety notes
2.4 Use in hazardous areas
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
23