ID/
Icons
Diagnostic
Action
Comments
79
Auto filtering
Check that the flowmeter is operated within its
specifications. Check other alarms to rule out
HW malfunction.
87
The sensor is stabilizing
Check sensor cable connection. Wait 20 sec‐
onds. If the status remains 'Coming' then turn
off the power, wait 5 seconds and turn on the
power again. If the failure continues then con‐
tact your local Siemens representative
10.2.2
Transmitter diagnostic events
Transmitter diagnostic events
ID/
Icons
Diagnostic
Action
Comment
96
Mass flow
Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'.
97
Mass flow
Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
98
Mass flow
Value below warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Lower warning limit'
99
Mass flow
Value below alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
100
Volume flow
Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
Diagnosing and troubleshooting
10.2 Fault codes and corrective actions
MASS 2100 & FC300 (FCT030)
194
Operating Instructions, 06/2017, A5E39789040-AA