ID/
Icons
Diagnostic
Action
Comment
176
Sensor
Sensor type incompatible. Please replace sen‐
sor.
177
Device is starting
Please wait until startup is finished. Startup time
see manual.
178
Transmitter
FW invalid. A component does not have the ex‐
pected FW version. Start a product firmware
update to update the component version.
179
Alarm class
Alarm class simulated. Disable Simulation be‐
fore returning to normal operation.
No detailed information avail‐
able in view Active diagnostic
events. Icon depends on simu‐
lated alarm class resp. NA‐
MUR status signal and the pri‐
ority in case of multiple alarm
classes simulated.
181
SensorFlash
SensorFlash Chkdsk failed. Start Chkdsk
again. If error still exist replace SensorFlash.
182
Communication interface
FW invalid. A component does not have the ex‐
pected FW version. Start a product firmware
update to update the component version or re‐
place the component.
183
CH2
Input current too low. Check wiring and signal
of connected sensor or output source to input
channel.
If Operation mode is config‐
ured to Current input.
184
CH2
Input current too high. Check wiring and signal
of connected sensor or output source to input
channel.
If Operation mode is configur‐
edto Current input
185
CH2
External failure. Connected sensor or output to
input channel is out of operation range. Please
check connected sensor or output source.
If Operation mode is config‐
ured to Current input
Diagnosing and troubleshooting
10.2 Fault codes and corrective actions
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
203