● Sensor and transmitter are connected to the potential equalization throughout the
hazardous area.
● EN/IEC 60079-14 is considered for installation in hazardous areas.
Further information and instructions including approval-specific special conditions for safe use
in Ex applications can be found in the certificates on the accompanying literature CD and at
the product web page (
WARNING
Laying of cables
Explosion hazard
Cable for use in hazardous areas must satisfy the requirements for having a proof voltage of
at least 500 V AC applied between the conductor/ground, conductor/shield and shield/ground.
Connect the devices that are operated in hazardous areas as per the stipulations applicable
in the country of operation.
WARNING
Field wiring installation
Ensure that the national requirements of the country in which the devices are installed are
met.
2.4.6
Maximum temperature specifications for Ex use
MASS2100 remote sensor
Temperature classification with and without dust is related to the process temperature and
ambient temperature as listed below.
The maximum allowable process fluid temperatures with respect to temperature class for the
device when used with potentially explosive gases.
Max media temperature [°C] versus temperature classification (T-ambient: -20 to +50 °C)
Maximum Process Temperature per Temperature Class (°C)
Di1/1.5/2.1/3
Di6
Di15
T6
75
46
38
T5
100
100
100
T4
135
135
135
T3
180
180
180
Additionally, the maximum surface temperature of the overall device shall be:
● For dust application, maximum surface temperature = 135°C
● For media temperature above 135°C surface temperature = media temperature
Safety notes
2.4 Use in hazardous areas
MASS 2100 & FC300 (FCT030)
24
Operating Instructions, 06/2017, A5E39789040-AA