Fraction (if available)
Sensor type
Sensor size
Unit
Default value
Upper Limit Alarm and Upper Limit Warning
FC400
DN 15
Mass flow Kg/s
2,209
Volume flow m
3
/s
0,0225
DN 25
Mass flow Kg/s
6,136
Volume flow m
3
/s
0,0626
DN 50
Mass flow Kg/s
24,54
Volume flow m
3
/s
0,250
DN 80
Mass flow Kg/s
62,83
Volume flow m
3
/s
0,641
DN 100
Mass flow Kg/s
180,56
Volume flow m
3
/s
1
DN 150
Mass flow Kg/s
298,61
Volume flow m
3
/s
2,3
MASS2100
1
Mass flow Kg/s
n/a
Volume flow m
3
/s
n/a
1.5
Mass flow Kg/s
0,022
Volume flow m
3
/s
0,00045
2.1
Mass flow Kg/s
0,043
Volume flow m
3
/s
0,00088
3
Mass flow Kg/s
0,088
Volume flow m
3
/s
0,0018
FC300 DN4 HP
2
Mass flow Kg/s
n/a
Volume flow m
3
/s
n/a
FC300 DN4 C22
3
Mass flow Kg/s
0,088
Volume flow m
3
/s
0,0018
FC300 DN4 316
3.5
Mass flow Kg/s
0,120
Volume flow m
3
/s
0,0025
MASS2100
6
Mass flow Kg/s
0,353
Volume flow m
3
/s
0,0072
15
Mass flow Kg/s
2,209
Volume flow m
3
/s
0,0451
Technical reference
A.1 Sensor dimension dependent default settings
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
265