AC MOTOR DRIVE 

Operation Manual

 

 
 

 
 

 

 

 

 

 

RM6F5 series 

 

 

Summary of Contents for RM6F5 series

Page 1: ...AC MOTOR DRIVE Operation Manual RM6F5 series ...

Page 2: ...Quality Satisfaction Improvement Innovation http www rhymebus com tw 2014 03 03 Edition 2018 10 24 Revised ...

Page 3: ...ease do read and follow specific instructions contained in this manual before using the product The manual shall be placed on the top of the machine and all the setup parameters and reference numbers must be properly recorded in Attachment 3 to facilitate future maintenance and repairs PREFACE ...

Page 4: ...e tasks Although the mark may indicate minor damages serious damages or injuries may be possibly incurred if the caution is not under user s attention Installation CAUTION a The installation shall take place only on top of the metal surface or any material with the fire resistant Any place or location of high temperature moist oil and gas cotton fiber metal powder and erosive gas shall be avoided ...

Page 5: ... the thermal relay between the individual motor and the drive when using one drive to propel several motors k Do Not connect phase advance capacitor surge absorber or non three phase motor to drive s U T1 V T2 W T3 side l AC reactor ACL installation is required when the power capacity exceeds 500kVA or 10 times or more than the drive rated capacity m After power off 30HP below models must wait at ...

Page 6: ...s d The drive can produce high frequency outputs Before adjusting the frequency please check the specifications of motor carefully to prevent the motor from unexpected damages e If any of the protective functions have been activated and the start command is set to terminal control F_001 0 or 1 First remove the case and check if the all running commands set to OFF Then press the OFF RESET key to re...

Page 7: ...ant pressure e Dry run protection f Out of curve operation and excessive outlet pressure alarm g Pipe Leakage differential pressure automatic adjustment start and stop h User friendly advanced control mode i System control mode parameterization set Various constant pressure control modes are set within and you only need to set simple parameters to switch into a different control mode j Process coo...

Page 8: ...Signal Distributor Control 44 2 4 4 Multi pump Control S mode Application 45 Chapter 3 The Setting of Keypad 46 3 1 Functions of Keypad KP 605 46 46 3 2 The Operation of Keypad KP 605 and Monitor Mode 48 Chapter 4 Parameter List 55 Chapter 5 Parameter Setting Description 71 5 1 The Keypad Setup 71 5 2 Preset Speed Setup 78 5 3 Multi Speed Accel Decel Time Setup 80 5 4 V F Pattern Setup 82 5 5 Anal...

Page 9: ...ss 124 6 12 Sequential Operation Control 125 6 12 2 Operation sequential control 126 Chapter 7 Communication Description 128 7 1 Communication wiring 128 7 2 Communication Setting 128 7 3 Communication Protocol 128 7 4 Message Format 129 7 5 CRC Checksum Algorithm 132 7 6 Processing Time of Communication Transmission 133 7 7 Communication Troubleshooting 134 7 8 Drive Registers and Command Code 13...

Page 10: ...Appendix I Outline Dimension Drawing of Drives 175 Attachment 1 Dimension of Keypad KP 605 179 Attachment 2 Default Value List 180 Attachment 3 Setting Memo 188 Attachment 4 Fault Display 192 ...

Page 11: ...pe etc 3 Check up the nameplate as below example by RM6F5 2001 of the drive to verify the product descriptions with the order specification Rhymebus Corporation TAIWAN BXXXXXXXX 0041 d AZXXXXXX 3PH 200 240V 0 1 120Hz 4 2A 3PH 200 240V 5A 50 60Hz RM6F5 2001B3 SERIAL NO PGM NO OUTPUT INPUT TYPE Model Number Input Power Specs Output Current Capacity Software Number Product Serial Number ISO 9001 IP20...

Page 12: ...5 Maximum applicable motor HP kW 1 0 75 2 1 5 3 2 2 5 3 7 7 5 5 5 10 7 5 15 11 Rated output capability kVA 1 6 2 6 3 8 5 8 9 5 12 16 Rated output current A 4 2 6 8 10 15 2 25 31 42 Rated output voltage V Three phase 200 240V Range of output frequency Hz 0 1 120 00Hz Power source ψ V Hz Three phase 200 240V 50 60Hz Input current A 5 8 12 18 30 41 55 Permissible AC power source fluctuation 176 264V ...

Page 13: ... rated output current for 1 min Cooling method Fan cooling Applicable safety standards Protective structure IP20 IP00 IP20 OPTION Weight Mass kg 5 7 16 16 16 17 40 41 44 Model name RM6F5 2125 2150 2200 2250 Maximum applicable motor HP kW 125 90 150 110 200 160 250 200 Rated output capability kVA 132 154 223 267 Rated output current A 346 405 585 700 Rated output voltage V Three phase 200 240V Rang...

Page 14: ...ethod Nature cooling Fan cooling Applicable safety standards Protective structure IP20 UL open type IP20 Weight Mass kg 1 8 1 8 1 9 2 2 5 3 5 4 5 6 Model name RM6F5 4025 4030 4040 4050 4060 4075 4100 4125 Maximum applicable motor HP kW 25 18 5 30 22 40 30 50 37 60 45 75 55 100 75 125 90 Rated output capability kVA 28 34 43 56 66 82 105 134 Rated output current A 37 45 56 73 87 108 138 176 Rated ou...

Page 15: ...V Three phase 380 480V Range of output frequency Hz 0 1 120 00Hz Power source ψ V Hz Three phase 380 480V 50 60Hz Input current A 196 217 282 355 385 440 540 650 800 900 Permissible AC power source fluctuation 332 528V 50 60Hz 5 Overload protection 120 of drive rated output current for 1 min Cooling method Fan cooling Applicable safety standards Protective structure IP00 IP20 OPTION IP00 Weight Ma...

Page 16: ...l braking resistor connected braking torque is approximately 100 Acceleration deceleration time 0sec coast to stop 0 0 3200 0sec independent setting of the acceleration deceleration The setting of accel decel time from 0 to 60Hz is 0 015sec 19 200 000sec 222 days V F pattern Linear Square curve 1 7th power curve 1 5th power curve V F pattern 2 V F points V F pattern can be adjusted by analog input...

Page 17: ...g pressure External indicator DM 501 Independent external display can be added for up to three sets 96mm 48mm 5 digits to show output frequency frequency command output voltage DC bus voltage output current terminal status and heat sink temperature Protections Fault protection Error trip messages of drive EEPROM error EEr A D converter error AdEr Fuse open SC Under voltage during operation LE1 Dri...

Page 18: ...rature level setting for other models Environment Atmosphere Non corrosive or non conductive or non explosive gas or liquid and non dusty Surrounding temperature 10 C 14 F 40 C 104 F Non freezing and non condensing Storage temperature 20 C 4 F 60 C 149 F Relative humidity 90 RH or less No condensing atmosphere Vibration Less than 5 9m sec 0 6G Altitude Less than 1000m 3280 ft ...

Page 19: ...ifications of motor please refer to 1 2 RM6F5 standard specifications of drives 2 1 4 Motor The specifications of motor are determined from the requirement Please be cautious to the motor rated current that must not exceed the drive current 2 2 Installing the Drive For the safe operation of the drive please be cautious to the environmental conditions where the drive is going to be installed 2 2 1 ...

Page 20: ... below figure 1 and figure 2 a Internal cooling Outlet Fan Outlet Fan Intlet RM5G P Driver RM5G P Driver Outlet Fan Outlet Fan Intlet Drive Drive Correct Incorrect Inlet Inlet Outlet Intlet Outlet Fan Fan Guide RM5G P Driver RM5G P Driver Outlet Intlet Outlet Fan Fan RM5G P Driver RM5G P Driver Drive Drive Drive Drive Correct Incorrect Inlet Inlet Figure 1 Drive mounting inside the cabinet control...

Page 21: ...rive Drive Drive Drive Correct Incorrect Inlet Inlet Inlet Inlet Outlet Outlet Intlet Intlet RM5G P Drive Fan Fan Outlet Intlet Intlet RM5G P Drive Fan Outlet Correct Correct Drive Drive Inlet Inlet Inlet Inlet Figure 2 Drive mounting inside the cabinet control panel Note The external cooling is suitable for 2007 4010 above Please ensure all air vents to be ventilated using the external cooling ...

Page 22: ...dd any phase advanced capacitor RC LC or other capacitance component between the drive and motor to avoid any accidents 2 2 5 Cleaning of Environment The installed location of drive must consider the ventilation cleanliness and moisture 2 2 6 Operator Only the qualified personnel can perform the operation and troubleshooting 2 2 7 Drive Supporting Frame option Please refer to opage 172 a Applicabl...

Page 23: ...istor option GND Analog Output Terminal DC 0 10V 1 COM R L1 S L2 Current Input for Frequency Setting Default DC 4 20mA Voltage Input for Frequency Setting Default DC 0 10V JP4 Multi pump Control Terminal P DX DX FG P24 JP5 ON 1 DSW3 Multi function Input Terminal 2 Multi function Input Terminal 3 Multi function Input Terminal 4 G T L3 3 1 JP5 SINK SOURCE selection The signal input selection of mult...

Page 24: ...equency Setting Default DC 4 20mA Voltage Input for Frequency Setting Default DC 0 10V JP4 Multi pump Control Terminal P DX DX FG P24 JP5 ON 1 DSW3 Multi function Input Terminal 2 Multi function Input Terminal 3 Multi function Input Terminal 4 T L3 3 N Braking Resistor option Jumper P PR P1 DC Reactor DCL option 1 JP5 SINK SOURCE selection The signal input selection of multi function input termina...

Page 25: ...COM R L1 S L2 Current Input for Frequency Setting Default DC 4 20mA Voltage Input for Frequency Setting Default DC 0 10V JP4 Multi pump Control Terminal P DX DX FG P24 JP5 ON 1 DSW3 Multi function Input Terminal 2 Multi function Input Terminal 3 Multi function Input Terminal 4 PE T L3 3 Jumper 1 JP5 SINK SOURCE selection The signal input selection of multi function input terminal please see the se...

Page 26: ... DX FG P24 JP5 ON 1 DSW3 Multi function Input Terminal 2 Multi function Input Terminal 3 Multi function Input Terminal 4 PE R L1 S L2 T L3 DCL 4 ACL Jumper 4 3 1 JP5 SINK SOURCE selection The signal input selection of multi function input terminal please see the section 2 3 2 SINK SOURCE Definition 2 JP4 I V selection I position Iin GND terminal is inputted with the current signal default V positi...

Page 27: ...re a and b show two examples by using a switch to control X1 to X4 FWD or REV terminals with sink or source mode 2 3 3 Using a PLC Circuit There are two ways of connection for multi function input terminals by PLC circuit SINK NPN logic X1 X4 COM FWD REV Drive 24V 0V SOURCE PNP logic X1 X4 COM FWD REV Drive 24V Jumper at 1 2 position SINK mode b Jumper at 2 3 position SOURCE mode PLC NPN PLC PNP 0...

Page 28: ...e outputs to motor terminals Output three phase variable frequency and voltage to motor Power and Braking P NA E Dynamic brake unit terminal The terminals can connect to dynamic braking unit option PA EA NA E P N P PR External braking resistor terminal The terminals can connect to external brake resistor option P PR PA EA PR P P1 External reactor terminal The terminal can connect to DC reactor DCL...

Page 29: ...in kgf cm Grounding terminal size Tightening torque lb in kgf cm RM6F5 ______ 2001 2002 2003 2005 4001 4002 4003 4005 4007 M4 13 8 15 M4 13 8 15 2 Grounding MCCB Grounding Resistor Motor Jumper Model number Terminal screw size Tightening torque lb in kgf cm Grounding terminal size Tightening torque lb in kgf cm RM6F5 ______ 2007 2010 2015 2020 4010 4015 4020 4025 4030 M5 20 8 24 M4 13 8 15 ...

Page 30: ...cm Grounding terminal size Tightening torque lb in kgf cm RM6F5 ______ 2025 2030 2040 2050 4040 4050 4060 4075 M6 69 4 80 M5 20 8 24 4 PE E P Grounding MCCB Motor Grounding T S L3 L2 R L1 W T3 U T1 T2 V N P P1 Model number Terminal screw size Tightening torque lb in kgf cm Grounding terminal size Tightening torque lb in kgf cm RM6F5 ______ 2060 2075 2100 4100 4125 4150 M8 104 120 M8 104 120 ...

Page 31: ...Model number Terminal screw size Tightening torque lb in kgf cm Grounding terminal size Tightening torque lb in kgf cm RM6F5 ______ 2125 2150 2200 2250 4175 4200 4250 4300 4350 4420 4500 4600 4700 M12 347 400 M8 104 120 Be cautious of the electrodes of DBU when connecting to PA EA NA EA terminals of drive to avoid any possible damages to drive ...

Page 32: ...pplied current is 20mA GND Common terminal for analog input control Grounding terminal for control power P12 12V P24 and analog input terminal Vin Iin Input terminals FWD Forward command terminal Connect the FWD and COM terminals for forward operation F_001 0 1 2 REV Reverse command terminal Connect the REV and COM terminals for reverse operation F_001 0 1 2 X1 Multi function input terminal 1 Conn...

Page 33: ...tact The function is set by F_061 Capacity AC250V 0 5AMax cosθ 0 3 Tc2 Common terminal for Ta2 Y1 Multi function output terminals open collector type The function is set by F_058 F_059 Capacity DC48V 50mAMax Y2 CME Common terminal of Y1 Y2 FG A8 Connect the shielded net to FG A8 and avoid the reflective signal to interfere the signal FM_P Reserved e Control Terminals and Switch for Communication A...

Page 34: ... KP 605 power 0V Only for KP 605 linking 8 Note 1 The terminal resistor 100Ω selection is set by DSW1 Default setting ON Note 2 When using multiple sets of drive connect all the DX DX terminals of each drive by series and connect the shielded net of the connection wire to FG terminal Note 3 The function of terminal resistor is to terminate the electric signal and avoid the reflective signal to int...

Page 35: ...01 socket CN3 Digital keypad KP 605 RJ 45 socket RS 485 communication interface choose one of the two options TB1 Input Output terminals TB2 Multi function output terminals relay type TB3 Connection terminals for multi pump control RS 485 communication interface choose one of the two options JP1 Input impedance selection of Iin close 250Ω open 500Ω Default close JP4 Input signal type selection of ...

Page 36: ...al indicator DM 501 socket CN2 Digital keypad KP 605 RJ 45 socket RS 485 communication interface choose one of the two options TB1 Input Output terminals TB3 Connection terminals for multi pump control RS 485 communication interface choose one of the two options JP1 Input impedance selection of Iin close 250Ω open 500Ω Default close JP4 Input signal type selection of Iin voltage current Default cu...

Page 37: ... length between drive and motor must keep as short as possible The parasitic capacitance effect is minor within 10 meters The drive should install an AC reactor ACL on the side of drive output terminals U T1 V T2 W T3 and decrease the switching frequency if the wiring length is over 30m c If the altitude over than 1000m The relationship between drive s rated current and altitude are shown as below...

Page 38: ...mm 2001 5 10 2 0 0 75 1 25 2 0 2002 8 15 2 0 2 0 2003 12 20 2 0 2 0 2005 18 30 3 5 3 5 2007 30 50 5 5 5 5 2010 41 75 8 8 2015 55 100 14 14 2020 66 125 22 22 2025 85 150 22 22 2030 103 175 38 38 2040 128 200 60 60 2050 176 300 80 80 2060 200 350 100 100 2075 240 400 60 2 60 2 2100 280 500 100 2 100 2 2125 330 500 150 2 150 2 2150 380 600 200 2 200 2 2200 550 800 200 2 200 2 2250 660 1000 250 2 250 ...

Page 39: ... 60 4100 155 250 80 80 4125 177 300 100 100 4150 196 300 60 2 60 2 4175 217 350 100 2 100 2 4200 282 400 100 2 100 2 4250 355 600 150 2 150 2 4300 385 600 200 2 200 2 4350 440 700 250 2 250 2 4420 540 800 250 2 250 2 4500 650 1000 325 2 325 2 4600 800 1200 325 2 325 2 4700 900 1200 325 2 325 2 Cautions i Please refer to the local electrical code with respect to the wiring the loading and continuit...

Page 40: ...nsducer JP4 ON DSW3 1 P24 Iin DX DX FG JP1 Drive 0 Setting Description Content Func F_015 Selection of Parallel Control Mode 1 Single pump F_016 Set Drive s No in Parallel Control 0 Drive 0 JP1 JP4 Selection JP1 Impedance selection of Iin Open 500Ω Close 250Ω Open JP4 Input signal type selection of Iin Voltage Current I position Terminal Resistor Switch DSW3 ON position ...

Page 41: ... mode or 3 F mode or 4 M mode F_016 Set Drive s No in Parallel Control 0 Drive 0 JP1 JP4 Selection JP1 Impedence selection of Iin Open 500Ω Close 250Ω Open JP4 Input signal type selection of Iin Voltage Current I position Terminal Resistor Switch DSW3 ON position Auxiliary Drive 1 2 3 Setting Description Content Func F_015 Selection of Parallel Control Mode 2 E mode or 3 F mode or 4 M mode F_016 S...

Page 42: ... control 0 Drive 0 JP1 JP4 Selection JP1 Impedence Selection of Iin Open 500Ω Close 250Ω Open JP4 Input Signal Type Selection of Iin Voltage Current I position Terminal Resistor Switch DSW3 ON position Auxiliary Drive 1 2 3 Setting Description Content Func F_015 Selection of Parallel Control Mode 2 E mode or 3 F mode or 4 M mode F_016 Set Drive s No for Parallel Control 1 JP1 JP4 Selection JP1 Imp...

Page 43: ...Selection JP1 Impedence selection of Iin Open 500Ω Close 250Ω Open JP4 Input signal type selection of Iin Voltage Current I position Terminal Resistor Switch DSW3 ON position Auxiliary Drive 1 2 3 Setting Description Content Func F_015 Selection of Parallel Control Mode 2 E mode or 3 F mode or 4 M mode F_016 Set Drive s No for Parallel Cntrol 1 JP1 JP4 Selection JP1 Impedence selection of Iin Open...

Page 44: ...5 AO5 FG 24V Iin G24 FG 24V Iin G24 FG NFB Drive 2 Drive 0 Drive 3 Note 1 ACE S12 signal distributor can be made input current signal covert into DC voltage meanwhile distributing five set of output output can switch current DC 4 20mA or DC 0 10V signal To reach constant pressure output signal will distribute the signal to drives maximum 4 drives 2 Wiring First pressure sensor connect PT1 and alte...

Page 45: ... 0 lead drive F_052 Multi input terminal setting X1 17 multi pump start command 1 F_053 Multi input terminal setting X2 18 multi pump start command 2 F_054 Multi input terminal setting X3 19 multi pump error command 1 F_055 Multi input terminal setting X4 20 multi pump error command 2 F_060 Multi output terminal setting Ta1 Tb1 15 multi pump start 1detection F_061 Multi output terminal setting Ta2...

Page 46: ...ng OFF RESET 3 Parallel connection error flashing SV Setting pressure indicator Indicate the setting pressure PV Actual pressure indicator Indicate the actual pressure Running Operation indicator Blinking Under acceleration or deceleration ON Constant speed OFF Stop HAND ON Manual mode standby indicator ON Manual mode Drive is standing by OFF Auto mode Stop AUTO ON Auto constant pressure standby i...

Page 47: ...ure control UP key Change functions and parameters DOWN key AUTO ON Auto constant pressure control Starting the inverter to auto constant pressure mode OFF RESET Off Reset key 1 Drive stops Cut off the output signal of U T1 V T2 W T3 terminals 2 Error reset Note KP 605 cables Only used with 8 pin telephone cable flat or Cat 5e cable AMP 8 pin telephone cable The cable length must be within 5 meter...

Page 48: ...below table by default setting Operation Steps Display 1 Start the drive and enter the monitor mode SV KEYPAD PV Running 2 Press PROG key and enter the function setting mode SV KEYPAD PV Running 3 Press FUN DATA key and enter the parameter setting mode SV KEYPAD PV Running 4 Press FUN DATA key and return to the function setting mode SV KEYPAD PV Running 5 Press PROG key and return to the monitor m...

Page 49: ... Monitor Mode FUN DATA FUN DATA PV Running SV KEYPAD PV Running SV KEYPAD PV Running SV KEYPAD PV Running SV KEYPAD PV Running SV KEYPAD PV Running SV KEYPAD FUN DATA FUN DATA Display 4 DC Bus Voltage PV Running SV KEYPAD PV Running SV KEYPAD FUN DATA FUN DATA FUN DATA Display 8 Actual Pressure Display 7 SV PV FUN DATA The descriptions of monitor modes are shown as below table by default setting N...

Page 50: ...t sink temperature is shown as below figure X4 X3 REV X1 Y2 Y1 Ta2 Ta1 Tb1 X2 FWD Heat sink temperature Left Display Right Display grey color digit in above figure means blinking Right display The temperature of heat sink Left display 1 Blinking number 6 Indicate the Display 6 2 Horizontal line of seven segment displays X1 X4 FWD REV terminals Vertical line of seven segment displays Y1 Y2 Ta1 Tb1 ...

Page 51: ... example SV KEYPAD PV Running 2 Press FUN DATA key to enter parameter setting mode SV KEYPAD PV Running 3 Press key to decrease the value of F_001 from 3 default value to 2 SV KEYPAD PV Running 4 Press FUN DATA key and return to function setting mode SV KEYPAD PV Running 3 2 5 Operation at Monitor Mode In monitor mode user can change the value of setting pressure SV The operation steps are shown a...

Page 52: ... the parameters to keypad and then display the copy process on keypad SV KEYPAD PV Running 5 After completing the copy the keypad will display message and automatically back to function setting mode SV KEYPAD PV Running a 2 Parameter Write In Keypad parameter Drive Operation steps Display 1 In the monitor mode press PROG key to enter function setting mode SV KEYPAD PV Running 2 Press or key to sel...

Page 53: ... FUN DATA key to enter parameter setting mode SV KEYPAD PV Running 4 Press key to select and then press FUN DATA key to copy the parameters SV KEYPAD PV Running 5 After completing the copy the keypad will display message and automatically back to function setting mode SV KEYPAD PV Running When using copy parameter function please note F_015 F_016 F_091 parameter content can t copy to the slave b R...

Page 54: ...isplay 1 Press or key to select the function to F_194 Default Setting and then press FUN DATA key to enter parameter setting mode SV KEYPAD PV Running 2 Press key to select parameter and then press FUN DATA key to execute the saving SV KEYPAD PV Running 3 After completing the saving the keypad will display message and back to the function setting mode SV KEYPAD PV Running Restore the setting value...

Page 55: ...Communication interface 11 Keypad RUN key RS 485 Communication interface F_002 Frequency Command Selection 0 Frequency command by analog signal via terminal 1 Frequency command by keypad 2 Pressure command by keypad 3 Frequency command by RS 485 4 Pressure command by RS 485 0 4 2 75 F_003 Selection of STOP key Validity 0 Start command by terminal STOP key disabled 1 Start command by terminal STOP ...

Page 56: ... frequency correspond to the base voltage in V F pattern 0 1 400 0 0 1Hz 60 0 82 F_012 Base Voltage The voltage correspond to the base frequency in V F pattern 0 1 255 0 0 1V 220 0 Note1 82 0 1 510 0 380 0 Note2 F_013 Selection of Pump Shift Operation Parallel control 0 Disable 1 Shift the pump operation arriving the operating time F_024 2 Shift the pump operation after a drive stops 3 Both 1 and ...

Page 57: ...ency Parallel Control In multi pump control systems set the cut off frequency and start frequency for lead auxiliary drive stopping 0 0 60 0 0 1Hz 50 0 110 F_024 Pump Auto Shift Time Parallel Control The time of pump shift operation in multi pumps control system 0 240 1 hr 24 107 F_025 Cut off Time Parallel Control In multi pump control systems the detection time of pump departs from operation 0 0...

Page 58: ...uency F_017 F_043 0 00 1 00 0 01 0 00 83 F_044 FM Analog Output Signal Selection 0 Output frequency 1 Frequency command 2 Output current 3 Vin frequency command 4 Iin frequency command 0 4 0 87 F_045 FM Analog Output Gain Analog output gain ratio adjustment 0 00 2 00 0 01 1 00 88 F_046 Motor Overload Protection OL 0 Motor overload protection Disabled 1 Motor overload protection Enabled OL 2 Motor ...

Page 59: ...ency 11 Speed tracing from the setting frequency 12 Holding command 13 Under close loop control condition F_103 0 open loop selection 14 Reset the integrator at close loop control condition F_103 0 15 Stop command 16 Analog input source selection 17 Auxiliary Pump start command 1 18 Auxiliary Pump start command 2 19 Auxiliary Pump error command 1 P1_OL 20 Auxiliary Pump error command 2 P2_OL 21 Fl...

Page 60: ...the frequency detection level of multi function output terminal 0 0 400 0 0 1Hz 0 0 94 F_064 Automatic Boost Voltage Range According to the load condition adjust the output voltage of the V F Pattern 0 0 Off 0 0 25 5 0 1 1 0 97 F_065 System Overload Detection OLO 0 Disable 1 Enable OLO 0 1 0 98 F_066 System Overload Detecting Selection 0 Detection during constant speed only 1 Detection during oper...

Page 61: ... braking 0 150 of drive rated current 1 50 100 F_076 Time Interval of DC Braking at Stop Set the time for DC braking after drive stopped 0 0 20 0 0 1 sec 0 2 100 F_077 Time Interval of DC Braking at Start Set the time for DC braking before drive starts 0 0 20 0 0 1 sec 0 0 100 F_078 Operation Selection at Instantane ous Power Failure 0 Drive cannot be restarted 1 Drive can be restarted 0 1 0 100 F...

Page 62: ...racing current level the output frequency will trace downward 0 200 of drive rated current 1 150 101 F_089 Delay Time before Speed Tracing Set the output delay time before the speed tracing 0 1 5 0 0 1 sec 0 5 101 F_090 V F Curve in Speed Tracing Set the percentage of V F output voltage at the speed tracing 0 100 1 100 101 F_091 Fault Record Display the latest 5 error records 121 F_092 Parameter S...

Page 63: ...et the integration time for deviation adjustment 0 0 I control disabled 0 0 25 0 0 1 sec 1 2 114 F_107 Derivative Time D Set the derivative time for deviation adjustment 0 00 D control disabled 0 00 2 50 0 01 sec 0 00 114 F_108 Derivative Time of Feedback Set the derivative time for feedback signal 0 00 2 50 0 01 sec 0 00 114 F_109 Integration Upper Limitation Set the upper limitation value of int...

Page 64: ...nd F_120 to detect if a pump suffers from water shortage 0 250 1sec 60 117 F_122 Water Shortage Drive Shutdown Time Drive will auto restart after the time setting when a pump suffers from water shortage F_118 3 0 off 0 200 1min 5 117 F_123 Analog Input Selection F_103 0 F_103 0 0 3 0 86 0 Vin Iin Vin Frequency command Iin Feedback signal 1 Vin Iin 2 Iin Vin 3 Vin or Iin switch by multi function in...

Page 65: ...Setting 0 Disable 0 CLF Clear fault records dEF60 Restore the default value of drive for 60Hz dEF50 Restore the default value of drive for 50Hz Distributor A setting value for constant pressure setting single pump dEF52 Restore the default value of drive for 60Hz Distributor A setting value for constant pressure setting multi pump dEF53 Restore the default value of drive for 50Hz SAv Save the sett...

Page 66: ...el of fan activation 25 60 1 50 122 F_146 Minimum Operation Time of Fan Set the minimum operation time of fan when the fan stops 0 1 25 0 0 1 min 0 5 122 F_147 Over Pressure Disposal 0 Disable 1 Alarm Drive keeps operation 2 Alarm Drive stops output 3 Error trip Drive trips to stop 0 3 0 120 F_148 Over Pressure Level According to the setting value of F_007 Pressure Transmitter Setting to set the o...

Page 67: ...cy command 0 100 maximum of output frequency 1 100 106 F_163 Frequency Lower Limitation by Manual Mode Setting manual mode for lower limit of frequency command 0 100 maximum of output frequency 1 0 106 F_166 K Value of Flow Sensor Setting value accord with specification of flow sensor 0 1 100 0 1L Pulse 10 0 123 F_167 Rate of Flow Sensor Setting rate of flow sensor 0 00 2 00 0 01 1 00 123 F_168 Un...

Page 68: ...le 1 Enable 0 1 0 126 F_181 Date Time Setting Y Year 2000 2099 125 M Month 1 12 d Day 1 31 W Week Sun 7 SAt 6 H Hour 0 23 MM Minute 0 59 F_182 Date Time Setting Y Year M Month d Day W Week H Hour MM Minute ____ Reserved 125 F_183 Sequential Operation Mode 0 Every week 1 Every day 0 1 0 126 F_184 Sector 1 Sequential Operation S Level selection OFF ON OFF 126 W Week Sun 7 Sunday Mon 1 Monday TUE 2 T...

Page 69: ...t be adjusted with amount of current 1 If the drive is overloaded the switching frequency can be adjusted with amount of current 0 1 103 F_194 Default Setting 0 Disable 0 CLF Clear error records dEF60 Restore the default value of drive for 60Hz dEF50 Restore the default value of single pump constant pressure control application with 60Hz power source dEF52 Restore the default value of multi pump c...

Page 70: ... 30HP 15 0sec g 40HP above 30 0sec 4 When the setting value of switching frequency F0 81 exceeds 4 the drive must be de rating for usage or selecting the higher capacity of drive 5 Represents a contact N O Represents b contact N C 6 Setting function F_014 F_056 F_057 F_139 F_152 F_154 F_161 F_164 F_165 F_169 F_170 F_178 F_179 F_192 F_193 Reserved ...

Page 71: ... nomenclature 1 Drive model number 2 Drive running hours 3 Drive power supplying time 4 Software checksum code 5 Reserved F_001 Start Command Selection a F_001 0 I FWD and REV terminals both control the start command and rotation direction II Drive stops operation when FWD and REV terminals are simultaneously open circuit or short circuit SINK NPN mode FWD OFF stop ON forward running COM REV OFF s...

Page 72: ...N reverse RUN STOP REV FWD SOURCE PNP mode FWD OFF stop ON running COM REV OFF forward ON reverse RUN STOP REV FWD DC 24V c F_001 2 I Start command by keypad ON key Rotation direction command by FWD or REV terminal II Drive stops operation when FWD and REV terminals are simultaneously open circuit or short circuit SINK NPN mode FWD OFF stop ON forward COM REV OFF stop ON reverse FWD REV ...

Page 73: ...irection by the RS 485 communication interface Related control command refer to 7 8 Drive Registors and Command Code g F_001 9 Start command by RS 485 communication interface Rotation direction command by REV terminal Related control command refer to 7 8 Drive Registors and Command Code h F_001 10 Start command by FWD terminal Rotation direction command by RS 485 communication interface Related co...

Page 74: ...play blanking except Display 8 terminal status 2 The definition of rotation direction is according to IEC International Electrotechnical Commission standard Observing the motor from axle center side not the fan side The standard rotation direction Forward is clockwise U T1 V T2 W T3 DRIVE FWD REV COM DRIVE FWD REV COM U T1 V T2 W T3 U T1 V T2 W T3 U T1 V T2 W T3 Figure A Figure B EX F_001 0 Forwar...

Page 75: ... by function F_127 and F_128 b F_002 1 Frequency command by keypad I In keypad KP 605 the primary speed jog speed and preset speeds F_009 F_017 can be set during operation and the frequency command can be set under monitor mode II In keypad KP 605 the pot knob can be defined by speed control c F_002 2 Pressure command by keypad KP 605 d F_002 3 Frequency command by RS 485 Related control command r...

Page 76: ...on If the drive needs to be restarted cut off the wire between the terminals of the start command FWD or REV and COM and restart the drive again II Normal stop F_001 2 or 3 the start command by ON key of keypad KP 201C and the stop is controlled by STOP RESET key F_004 Setting Value SV Change Selection a F_004 0 In the monitor mode the setting value cannot be changed by KP 605 keypad to avoid poss...

Page 77: ...directly connected to the drive without connecting other power source 2 The setting range of F_099 F_101 is 0 6 and the significance is shown as below 0 Disable the indicator 1 Output frequency 2 Frequency command 3 Output voltage 4 DC bus voltage 5 Output current 6 Terminal status and heat sink temperature DM 501 cannot monitor the pressure setting and actual pressure 3 Please select twisted pair...

Page 78: ... OFF OFF OFF OFF Primary speed OFF OFF OFF ON Preset speed 1 OFF OFF ON OFF Preset speed 2 OFF OFF ON ON Preset speed 3 OFF ON OFF OFF Preset speed 4 OFF ON OFF ON Preset speed 5 OFF ON ON OFF Preset speed 6 OFF ON ON ON Preset speed 7 Note 1 X Don t care 2 The following chart shows jog speed having highest precedence and jog speed command is ON the motor is running at jog speed 3 Jog speed comman...

Page 79: ...e Preset speed 5 Preset speed 6 Primary acceleration time Preset speed 7 Primary deceleration time Jog speed Primary acceleration time Primary acceleration time The acceleration deceleration time of jog speed and preset speed 4 7 are according to the setting of primary acceleration deceleration time F_019 F_020 Jog speed control include start command When drive stop activating the jog speed comman...

Page 80: ...s and the preset speed acceleration deceleration time b The acceleration deceleration time of primary speed preset speed 4 7 and jog speed are controlled by the setting of primary acceleration deceleration time c The switch between primary accel decel and secondary accel decel can be selected by multi function input terminals Illustration is as follows Max output frequency F_017 Time Secondary acc...

Page 81: ...FWD terminal is open circuit III When F_003 set 1 pressing the OFF RESET key IV Press the OFF RESET key when start command by keypad e Set the S curve function depend on the application to buffer the impact during start stop acceleration and deceleration EX To buffer the impact when the object fall on the conveyor line or the running of elevator Frequency command Time Output frequency S curve time...

Page 82: ...ase voltage The setting must be according to the nameplate of motor 200V series 0 1 255 0V 400V series 0 1 510 0V F_017 Maximum Output Frequency RM5P series The setting range of max output frequency is 0 1 120 0 F_030 V F Pattern Selection a The settings are listed as below 0 Linear 1 Energy saving mode Auto adjust V F according to the loads 2 Square curve 3 1 7 th power curve Base freq Output vol...

Page 83: ...ncy upper limit F_042 Maximum output frequency F_017 F_043 Frequency Lower Limit Set the ratio of the frequency lower limit 1 00 maximum output frequency and the setting range is 0 00 1 00 Output frequency lower limit Frequency lower limit F_043 Maximum output frequency F0_17 Output frequency Frequency command 60 0Hz 60 0Hz 54 0Hz 54 0Hz 6 0Hz 6 0Hz Max output freq 60 0Hz Freq upper limit 0 90 Fre...

Page 84: ...cy 60 0Hz Maximum output frequency 60 0Hz Analog input gain 1 20 Analog input gain 0 80 Output Frequency Analog Command 60 0Hz 48 0Hz 0Hz 0Hz 0V 4mA 0V 4mA 10V 20mA Analog Command Output Frequency 10V 20mA 8 3V 17 3mA Gain 1 Gain 1 2 Gain 1 Gain 0 8 60 0Hz b F_103 0 Iin PV value Maximum transmitter F_007 x Analog input gain F_40 or F_127 EX If analog input bias F_041 or F_128 0 00 Maximum transmit...

Page 85: ...05 Example of reverse control application Analog Command 60 0Hz 60 0Hz 3 0Hz 3 0Hz 0V 4mA 0V 4mA 0 5V 4 8mA 10V 20mA Output Frequency Analog Command Output Frequency Bias 1 Bias 0 05 Bias 0 05 Bias 1 10V 20mA Max output freq 60 0Hz Analog input gain 0 00 Analog input bias 1 00 Analog command 0V 4mA 10V 20mA 60 0Hz 0Hz Frequency command b F_103 0 The corresponding PV value of Iin analog input bais ...

Page 86: ...alog input signal when the frequency command by analog input terminals F_002 0 b The larger setting value will cause the slower response c 0 Disable the filtering F_096 Analog Input Dead Band a When the noise of analog input signal is large appropriately increase the dead band to stabilize the frequency command But adjusting this function will reduce the tuning linearity of input signal b This set...

Page 87: ...ng output terminal FM or AM outputs DC 0 10V to correspond the frequency command the terminal will output when drive is operation or stop 2 Output current The analong output terminal FM or AM outputs DC 0 10V to correspond the output current max corresponding value is rated output current of drive 3 Vin analog input signal The analong output terminal FM or AM outputs DC 0 10V to correspond the sig...

Page 88: ... Analog output gain 1 20 10V 0V 21 25A 17A Output current 8V 10V 0V 0 0Hz 60 0Hz 50 0Hz Output freq or Freq command Analog output 10V 0V 50 0Hz Vin freq setting 0V 8V 60 0Hz Driver rated current 17A Analog output signal selection 2 Analog output gain 0 80 Analog output Maximum output freq 60 0Hz Analog output signal selection 3 Analog output gain 1 20 Analog output Analog output Maximum output fre...

Page 89: ...led OL 2 Overload protection for independent cooling fan type motor Enabled OL F_048 Motor Rated Current F_049 Motor No Load Current F_050 Motor Slip Compensation a The slip of motor is variable depending on the load When the load current is over the level of slip compensation the drive will compensate the output frequency to output constant speed The setting range is 9 9 10 0Hz b Compensation fre...

Page 90: ...rt stop in sequence when any terminal is activated 1 Jog command refer to F_039 2 Secondary accel decel time command refer to F_027 F_028 3 Multi speed level 1 command refer to F_032 F_038 4 Multi speed level 2 command refer to F_032 F_038 5 Multi speed level 3 command refer to F_032 F_038 6 Reset command When the drive trips to stop executing reset command can clear the fault 7 External fault com...

Page 91: ...mmand 10 Speed tracing from the maximum frequency Speed tracing from the maximum frequency F_053 10 Terminal start command FWD Decel time is 2 sec Delay Time before Speed Tracing F_089 The current level of speed tracing F_088 Normal accel time 0 1sec Speed tracing command X1 Max output frequency Output frequency Output voltage Output current The V F Pattern of Speed Tracing F_090 Return to normal ...

Page 92: ...mmand of preset speed 14 In closed loop control F_103 0 integrator reset 15 Stop command After the terminal is acted the drive will decelerate and stop 16 Analog input source selection Select Vin or Iin to as the analog input signal F_123 3 Vin or Iin 16 Terminals short circuited Vin Analog Input Source Terminals open circuited Iin Analog Input Source 16 Terminals short circuited Iin Analog Input ...

Page 93: ...ing Description 93 5 21 Flow sensor input Flow sensor input signal please refer to 6 11 Flow sensor description 22 Sequential operation start command please refer to 6 13 2 Sequential operation control description on page 122 ...

Page 94: ...AUTO ON the drive will detect at start Running detection F_060 1 Output terminal Ta1 Tb1 SV Start command Freq PV Time 2 Constant speed detection Detection at constant speed 3 Zero speed detection F_131 Constant speed detection range 0 0 10 0Hz 4 Frequency detection F_062 Frequency detection range 0 10Hz F_063 Frequency detection level 0 120Hz Output terminal Time Output freq Freq detection range ...

Page 95: ...Stall prevention detection Stall Prevention Level at the Constant Speed F_071 Outupt terminal Time Time Output current Output freq Stall Prevention Detection F_058 6 7 Low voltage detection LE DC bus voltage Output terminal Y1 LE abnormal status level Low voltage detection F_058 7 8 Braking transistor is active detection Detection when the DC bus voltage of drive is higher than the dynamic brake v...

Page 96: ...oltage Speed searching current level F_088 Output current Output terminal Delay time for speed searching F_089 normal V F The V F pattern of speed searching F_090 10 Restart after fault condition detection Restart after fault condition detection F_058 10 Fault condition Output freq Output current Output voltage Output terminal normal V F The V F pattern of speed searching F_090 Delay time for spee...

Page 97: ...e when F_015 is set to 5 Please refer to 2 4 4 multi pump control S mode on page36 17 Fan detection during operation Please refer to F_144 Fan control selection 5 10 Automatic Torque Compensation F_064 Automatic Boost Voltage Range 0 25 5V Dynamic compensation by voltage to avoid any insufficient voltage at heavy duty load The adjustment method is to minimize the output current by adjusting the pa...

Page 98: ...the system overload is detected 1 Drive trips after the system overload is detected F_068 System Overload Detection Level Setting the level of current for system overload detection and the setting range is 30 200 of drive rated current F_069 System Overload Detection Time a The detection of system overload is shown in the below chart Overload detection Overload detection level F_068 Current Time T...

Page 99: ...stant speed Stall prevention level at the acceleration F_070 Time Time Time Time Current Current Output frequency Output frequency Deceleration time for stall prevention F_073 Acceleration time for stall prevention F_072 Multi output terminal Y1 F_058 6 Stall prevention level at the constant speed F_071 Multi output terminal Y1 F_058 6 a The function of the stall prevention during the deceleration...

Page 100: ...ng frequency F2 33 the drive will stop by DC braking and the DC Braking Frequency at Stop F3 25 will be not active Start command Time interval of DC braking at start F_077 Time interval of DC braking at start F_076 Output frequency DC braking frequency at stop F_132 Time Time 5 14 Operation Selection at Instantaneous Power Failure F_078 Operation Selection at Instantaneous Power Failure a The sett...

Page 101: ...0 100 a When the drive current is greater than the current level of speed tracing F_088 the output frequency is tracing downwardly to reach the current level of speed tracing b The speed tracing function is mainly used for tracing the speed for the drive restart after instantaneous power failure flying start the drive fault restart or the speed tracing command is given by the input terminal c See ...

Page 102: ... Above 100HP 10kHz Switching frequency will be modulated with load automatically 1min Load current 80 90 100 Switching frequency 15K 12 5K 10K 7 5K Time 5 1min 1min 1min 1min 1min Switching frequency Load current F_082 Stop Mode 0 Ramp to stop 1 Coast to stop 2 Coast to stop DC braking When the value of F_082 is set to 2 the operation characteristic is shown as below figure DC voltage Time Output ...

Page 103: ...an the 90 of F_095 setting value the drive will display LE warning message After the power ON for drive the drive displays LE message when the power source is lower than the 70 of F_095 setting value F_098 Grounding Fault Protection GF 0 Disable 1 Enable F_097 Digital Input Response Time Range 1 16ms default 10ms If the signal length of digital inputs is smaller than the digital input response tim...

Page 104: ...accordance with the specification of the pump or can prevent the water pipe from harm by setting too high pressure According to the specification of the pump to set the operational pressure value F_007 F_008 Example Maximum pressure value of the pressure transmitter 10 0bar F_008 50 Maximum operational pressure of the drive F_007 10 0bar F_008 50 5 0bar F_114 Feedback Signal Trip Detection 0 Disab...

Page 105: ...n temporary When the multi function input terminal is set to 13 Under close loop control condition F_103 0 open loop selection F_126 Iin Range Selection 0 4 20mA 2 10V 1 0 20mA 0 10V According to the specification of pressure transmitter to select the Iin range F_127 Iin Gain Analog Input The gain ratio of analog input terminal Iin Set the gain ratio for the feedback signal from pressure transmitt...

Page 106: ...aul Mode under Close Loop Condition 0 Analog input terminal Vin 1 Keypad or key setting 2 Keypad setting knob 3 RS 485 Communication interface In close loop control select the speed command source when feedback signal is bypassed in temporary F_162 Frequency Upper Limitation by Manual Mode Setting Frequency Upper Limitation The drive only follow F_162 setting value Upper Limitation Manual Mode Max...

Page 107: ...e pump operating time of the sequential control in multi pump control Setting range 0 240hr 0 Disable drive will not execute sequential operation F_137 Delay Time at Pump Shifting The delay time setting is to remain the stable pressure of the system at the interchanging of the pump operation Default 10sec During the pump shifting the system pressure becomes unstable when one pump drive disengages ...

Page 108: ...ct this mode when installing or trial running the pump 5 Multi pump applications S modet Lead pump which have an automatic speed control auxiliary pump1 or pump 2 will follow setting condition to run AC power start operating to maintain constant pressure Start condition of sequential operation Lead Pump Auxiliary Pump1 Auxiliary Pump2 1 When lead pump run at full speed but PV value F_022 Start det...

Page 109: ...or pressed the OFF RESET key the drive with following number will become lead drive to order the command to other drives Func Name Description F_021 Launch Detection Time Parallel Control In multi pump control systems set the detection time of pump for parallel start up In multi pump control systems the standby pumps will parallel control in sequence when the operating drive runs at full speed for...

Page 110: ... Cut off Time of Parallel Control In multi pump control systems set the cut off time to cut off the pump operation 1 In multi pump control systems E mode or S mode when the output frequency is below the F_023 and maintaining the time interval F_025 the drive will depart from the parallel control system in sequence Last in First out Example Two pumps for parallel control F_015 2 E mode Output frequ...

Page 111: ... the condition of applications users can set the standing by number of drives to protect the system Setting range 0 3 units 0 disable The default parallel number of drives are 2 sets Valid setting of standing by drives as below F_150 Continuous Water Supply Control 0 Disable 1 Enable default F_151 Less Pumps set during Operation In multi pump control systems deploying the number of operating pumps...

Page 112: ...ater Usage Detection to detect if the water is used F_117 Pressure Dead Band Setting In constant pressure control mode F_103 0 drive will activate PID control when the feedback signal exceeds the dead band F_133 Drive Stop Frequency of Water Usage Detection When the operation frequency is lower than the setting value drive will ramp to stop 1 In constant pressure control mode drive will auto detec...

Page 113: ...mple SV 2 0bar F_087 0 3bar When PV actual pressure 1 7bar Drive starts When PV actual pressure 2 3bar Drive stops 1 In ON OFF control mode drive will start stop in accordance with the setting of F_087 2 When the drive is operating under ON OFF control mode There are two dots will be shown on display of keypad at SV and PV indicators 3 The positions of dots SV KEYPAD PV Running 2sec ON 2sec 2sec F...

Page 114: ...he drive will start to decelerate F_104 P Selection 0 P postposition 1 P preposition F_105 Proportional Gain P Set the gain value for deviation adjustment 0 0 P control disabled To adjust the stable time Increase the value Increase the response speed of constant pressure control system Decrease the value Reduce the oscillation and response speed F_106 Integration Time I Set the integration time fo...

Page 115: ...pper Limit F_043 Frequency Lower Limit PID_HALT Error F_102 PID Compensation Gain Gain F_002 Selection of Command 0 1 2 F_105 Proportional Gain P P F_104 P Selection 0 1 F_111 PID Offset Adjustment Bias F_109 Integration Upper Limitation F_110 Integration Lower Limitation F_107 Derivative Time D D P I F_103 PID Control Mode Selection 1 3 2 4 0 1 F_112 PID Buffer Space F_125 Signal Source Selection...

Page 116: ...n in the short period When the oscillation happens in the cycle that longer than the setting time of integration the integration setting is too strong causing the system oscillation Set longer time of integration to stabilize the system and reduce the oscillation Time After adjustment Before adjustment Response 4 Reducing the oscillation of continuous period If the system appears the continuous os...

Page 117: ...me for Water Shortage When the drive suffers from water shortage conditions the drive will trip to stop and display The drive will auto restart after the setting time of F_122 F_119 Water Shortage Detection by Pressure Level Set the pressure level to detect if pump suffers from water shortage conditions Detection engages when the drive runs at full speed 0 Disable F_120 Water Shortage Detection by...

Page 118: ...cavitation phenomenon appearing in pump systems Output frequency Actual pressure PV Setting pressure SV F_119 F_121 Fb Lo 6 5 2 Dry Running When the drive runs at full speed and the output current of the drive is lower than F_048 Motor Rated Current F_120 Water Shortage Detection by Current Level with a time interval F_121 Time of Water Shortage Detection the drive will trip to avoid dry running c...

Page 119: ...p in accordance with the setting of F_020 Primary Deceleration Time 1 Enable When the output frequency decreases to the setting of F_133 the drive will ramp to stop in accordance with the setting of F_028 Secondary Deceleration Time 1 The pump might produce noise when stopping due to the friction of the pump shaft seal Enable F_136 and adjust the suitable setting value of F_028 to reduce the noise...

Page 120: ...ing character Press the OFF RESET key to restart the drive again when drive trips to stop F_148 Over Pressure Level According to the setting value of F_007 Pressure Transmitter Setting to set the over pressure level Set the over pressure level in accordance with maximum pressure of water pipe or system F_149 Over Pressure Detection Time When the actual pressure exceeds over pressure level F_007 F_...

Page 121: ...en the setting value sets to 0 the drive will not restart after an error occurs If a drive is operating over 24hrs without any error trip the drive will automatically reset the counting number F_083 Time Interval of Drive Auto Restart Set the error tripping time interval before drive auto restarts for F_079 Auto Restart Selection of Error Trip when the drive trips to stop Unit 10sec Default value ...

Page 122: ... Overheat Pre alarm Level Set the warning level for overheating detection F_143 Drive Overheating Dead Band Set the temperature dead band of F_142 and F_145 F_144 Fan Control Selection 0 Forced air Fan will start running at drive power ON 1 Operation air Fan will start running when the drive is running 2 Temperature level setting Fan will start running when the temperature is over the setting leve...

Page 123: ...67 Flow Sensor Rate Set up the rate of flow sensor Range 0 00 2 00 default 1 00 F_168 Flow Sensor Display Unit 0 LPS l sec default value 1 CMH m3 hr 1 Flow sensor specification Pulse input type 2 Flow sensor formula Flow rate I sec Input pulses pulse sec Flow sensor K value I pulse Flow sensor rate 3 Flow sensor input signal can connect multi input terminal X1 X4 F_52 F_055 set 21 ...

Page 124: ...rrent in Minimum Flow IQmin Setting current in minimum flow IQmax Range 1 200 default value 30 F_176 Pump Flow Rate Compensation for Pipe Friction Loss HCOMP max Setting Pipe Friction Loss in maximum flow Range 0 1 160 0 bar default value 0 0 F_177 Response Time Compensation of Pipe Friction Loss Setting Response Time Compensation for Pipe Friction Loss Range 0 1 255 default value 40 1 Maximum flo...

Page 125: ... Monday tUE 2 Tuesday uEd 3 Wednesday tHU 4 Thursday F r i 5 Friday Sat 6 Saturday H Hour 0 23 Minute 0 59 Reserved When entering F_181function key to adjust the time FUN DATA key to switch the setting display Func Name Description Content Setting Range F_182 Time Display Y Year 2000 2099 Month 1 12 d Day 1 31 u Week SUn 7 Sunday H Hour 0 23 Minute 0 59 Reserved When entering F_182 function key to...

Page 126: ...ek setting H Hoursetting Minute setting C Pressurecommandsetting SL Inclinetime F_185 Setting Sector 2 of Sequencial Operation F_186 Setting Sector 3 of Sequencial Operation F_187 Setting Sector 4 of Sequencial Operation F_188 Setting Sector 5 of Sequencial Operation F_189 Setting Sector 6 of Sequencial Operation F_190 Setting Sector 7 of Sequencial Operation F_191 Setting Sector 8 of Sequencial O...

Page 127: ... from 1st sector The sequential operation will stop only when the start command of sequential operation control is OFF Example 2 Operating mode lets user set a weekly and four peirods can be set at most 0 8 16 Time hr Pressure command bar 2 bar 4 bar 6 bar Monday 1st section 2nd section 3rd section 4th section 0 Tuesday Thursday Wednesday Friday Saturday Monday Sunday 8 16 0 8 16 0 8 16 0 8 16 0 8...

Page 128: ...f over time detectoin F_159 Communication Overtime Disposal 0 Warning Cot Continue operation 1 Warning Cot Ramp to stop 2 Warning Cot Coast to stop F_160 Control Selection of Multi Function Input Terminals 0 Multi function input terminals selves 1 Multi function input terminals command by communication interface 7 3 Communication Protocol Serial data transmission is an asynchronous serial data tra...

Page 129: ...to multi registers Data Including start register several registers data length maximum 8 data data content maximum 16 bits Note Data length 1 byte others 1 word 2 bytes CRC Checksum Cyclical Redundancy Check performs XOR and bit shifting operations for all hexadecimal values in the message to generate the checksum code to verify the communication validity Checksum is to sum all message bits for 16...

Page 130: ...ve receives the host s command the drive returns 4 bytes data 2101H 5500H and 2102H 1770H to the host Caution The host cannot simultaneously broadcast 03H OP code to drives when multiple drives connected or all drives reject host s OP code 06H Write to single register Example Write a data 1770H into the drive register 2001H Message Code Host to Drive Address OP Code Drive Register Register Data CR...

Page 131: ...H OP code to all drives when multiple drives connected or drives reject drive s OP codes 10H Write to multi registers When multiple data need to write into the drive from the host the host can define how many registers and data to be written into the drive This example is illustrating 2 data 1011H and 1770H from the host to be written into 2 drive registers 2000H and 2001H Message Code Host to Dri...

Page 132: ...0 0 0 1 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1 1 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1 1 0 0 1 1 1 1 1 1 1 1 1 1 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 0 0 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 0 0 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 ...

Page 133: ...a001 else reg_crc reg_crc 1 7 6 Processing Time of Communication Transmission Host Drive Communication Starts Resets 10ms 10ms 5ms Note Time The communication waits for 10ms to start the communication transmission after the drive powers on or the communication function of the drive changes The drive needs 5ms processing time to return the message to the host after the message are received from the...

Page 134: ...t7 as 1 for the original command message but error code gives different values according to different types of errors The below table is describing types of error code Error Code Error Type Descriptions 0 0 Serial communication format error Parity error of serial communication 0 1 Data frame error of serial communication 0 2 Over bit error of serial communication 0 3 Modbus OP code error OP code i...

Page 135: ...b8 bA 000 Primary speed communication 001 Preset speed 1 010 Preset speed 2 011 Preset speed 3 100 Preset speed 4 101 Preset speed 5 110 Preset speed 6 111 Preset speed 7 bB Reserved bC bD 00 No use 01 b6 bA functions Note 1 10 Enable operation command 2 resister 11 Disable 01 and 10 bE bF Reserved 2001H Frequency command Primary frequency is set by communication unit 0 01Hz 2002H Operation comman...

Page 136: ...ressure protection OP 2101H Drive status 1 b0 b7 Reserved b8 1 Frequency control by communication b9 1 Frequency control by analog inputs bA 1 Operation command by communication bB 1 Parameter locking bC 1 Drive running status bD 1 Jog running status bE 1 Forward indication bF 1 Reverse indication 2102H Frequency command Monitor drive s frequency command unit 0 01Hz 2103H Output frequency Monitor ...

Page 137: ...og input bD 1 Primary speed by operation panel bE 1 Primary speed by UP DOWN command bF 1 Primary speed by communication 2301H Drive status 2 b0 Reserved b1 1 Constant speed b2 1 Zero speed b3 1 Frequency detection b4 1 System overload b5 1 Stall prevention b6 Reserved b7 1 Braking action b8 Reserved b9 Reserved bA 1 Error signal bB bF Reserved 2302H Reserved 2303H Fault record 1 Fault record 1 No...

Page 138: ...error 03H EEr1 Internal memory error 08H OC Drive over current 0CH OE Over voltage 0DH LE1 Under voltage during operation 0EH GF Grounding fault 0FH OH Drive overheat 10H OL Motor overload 11H OL1 Drive overload 12H OLO System overload 13H EF External fault 14H PAdF Keypad interruption during copy 16H ntcF Thermal sensor fault 17H OH2 Motor overheat 18H noFb PID feedback signal error 19H OL2 Drive...

Page 139: ...or Drive Start c The drive register to be written for start operation 2000H d The register data for start operation 0002H Address OP Code Drive Register Register Data MSB LSB MSB LSB 01H 06H 20H 00H 00H 02H 2 Forward rotation command a Create an icon or active button key on the host for Forward b Program the host with following code for Forward rotation control c The drive register to be written f...

Page 140: ...imary acceleration deceleration time Address OP Code Drive Register Register Data MSB LSB MSB LSB 01H 06H 20H 00H 00H 00H 7 9 3 Host Control to Drive Read Operation 1 Drive Error Trips Fault Code Example Drive error trips due to GF grounding fault and the fault message displayed at the host 1 The host sends the below codes to access the drive register to monitor drive faults read only one register...

Page 141: ...ster 2103H Number of register to read 1 0001H Message Code Host to Drive Address OP Code Drive Register Register Numbers to Readout MSB LSB MSB LSB 01H 03H 21H 03H 00H 01H b The drive returns the frequency output readouts to the host Output frequency readouts from the drive 2103H register data Return Code Drive to Host Address OP Code Data Byte 2103H Register Data MSB LSB 01H 03H 04H 0FH E1H c Pro...

Page 142: ...e output voltage and current are valid Press OFF RESET when completing all verifications D Switch off the power and wait for drive s power indicators off and then connect drive s U T1 V T2 W T3 terminals to the motor E Operate the motor with the drive by low speed after power ON to verify the validity of the motor rotation direction and then to slowly increase the motor speed F Motor start or stop...

Page 143: ...2HP drive for 1HP AC motor b Wiring of power Connect the single phase power line to R S terminals c Parameter settings Please reset below functions If the parameters are not modified the motor and drive could be possibly damaged F_048 Motor Rated Current 3 1A the setting must be based on the motor rated current F_068 System Overload Detection Level 80 the half of the default setting value 160 F_07...

Page 144: ... all parameters to default value and restart the drive Return the drive to repair when the fault cannot be eliminated AdEr SV KEYPAD PV Running A D converter error Please call customer service for drive repair SC SV KEYPAD PV Running Fuse open Drive internal fuse open IGBT power module damage Please call customer service for drive repair SC1 SV KEYPAD PV Running Short circuit protection The output...

Page 145: ...lity Check if the motor operated in over rated condition Check if the the acceleration time is too short GF SV KEYPAD PV Running Grounding fault The three phase output current is unbalance and exceeding the detection level of grounding fault Grounding fault protection F_098 The output terminal of the drive is short or grounding Check the insulation value of motor and the shield of motor s wire OE ...

Page 146: ...o low The current setting of motor s rated current is invalid Check the load of motor Check if the acceleration or deceleration time is too short Check if V F setting is proper Check if the rated current setting is valid OL1 SV KEYPAD 設定值 PV 實際值 Running Drive overload Operation current exceeds 150 of drive s rated current for 1 minute Motor overload The voltage setting of V F pattern is too high o...

Page 147: ...connecting wire of keypad no Fb SV KEYPAD PV Running PID feedback signal error The feedback signal wire is loosen tripped Check the feedback signal wire OP SV KEYPAD PV Running Over pressure The setting value of F148 is not appropriate Pump oulet pressure is too high The water valve shut down immediately The pressure sensor is abnormal Check whether the setting value of F148 is appropriate Check w...

Page 148: ...mmand db SV KEYPAD PV Running Dynamic brake over voltage The internal DC bus voltage of drive is over the protection level DC bus voltage is too high Increase the deceleration time or use high torque braking method and add dynamic brake unit PrEr SV KEYPAD PV Running Program fault Check the software version of drive Ht SV KEYPAD PV Running Drive overheating The temperature of drive s heat sink rea...

Page 149: ...version OP SV KEYPAD PV Running Over pressure Over pressure level F_148 Detect time of over pressure F_149 The setting value of F148 is not appropriate Pump oulet pressure is too high The water valve shut down immediately The pressure sensor is abnormal Check the settings of function F_148 F149 Check the pressure of pump system and water pipes CPyF SV KEYPAD PV Running Parameter copy fault In the ...

Page 150: ...MHz 10MHz R S T L1 L2 L3 U V W T1 T2 T3 P P1 DC reactor DCL Improve power factor of driver The ACL can reduce the leakage current of motor effectively It is used as the motor is far away from the drive Reduce radiation interference The range of limited frequency is 1MHz 10MHz Motor RFI Filter CAUTION 1 When the drive requires the following equipment please select the proper external equipment The ...

Page 151: ...armonic current will interfere the drive Thus add the ACL at the input terminal R L1 S L2 T L3 of the drive is required d When multiple drives of high horse power are used due to harmonic wave exerted adding ACL at the input terminal R L1 S L2 T L3 of the drives is required to prevent the drives from the possible interference and power quality deterioration e When the cable length between the driv...

Page 152: ...0 05 100 RM6F5 4025 0 13 50 0 13 50 RM6F5 2030 0 05 100 0 05 100 RM6F5 4030 0 13 50 0 13 50 RM6F5 2040 0 05 100 0 035 150 RM6F5 4040 0 13 50 0 07 75 RM6F5 2050 0 035 150 0 025 200 RM6F5 4050 0 07 75 0 05 100 RM6F5 2060 0 025 200 0 025 200 RM6F5 4060 0 05 100 0 05 100 RM6F5 2075 0 025 200 0 015 300 RM6F5 4075 0 05 100 0 035 150 RM6F5 2100 0 015 300 0 013 400 RM6F5 4100 0 035 150 0 025 200 RM6F5 212...

Page 153: ...RM6F5 2030 0 4 100 RM6F5 4030 0 9 50 RM6F5 2040 0 4 100 RM6F5 4040 0 9 50 RM6F5 2050 0 25 150 RM6F5 4050 0 5 75 RM6F5 2060 0 2 200 RM6F5 4060 0 4 100 RM6F5 2075 0 2 200 RM6F5 4075 0 4 100 RM6F5 2100 0 15 300 RM6F5 4100 0 25 150 RM6F5 2125 0 177 400 RM6F5 4125 0 2 200 RM6F5 2150 0 177 400 RM6F5 4150 0 2 200 RM6F5 2200 0 09 800 RM6F5 4175 0 15 300 RM6F5 2250 0 09 800 RM6F5 4200 0 15 300 RM6F5 4250 0...

Page 154: ...5A A 109 86 58 77 111 95 135 16 8 6 2 0 0 2mH 30A A 109 86 58 77 111 95 135 16 8 6 2 2 0 13mH 50A B 150 80 70 85 152 126 130 16 8 6 4 6 0 07mH 75A B 150 80 68 85 151 126 131 16 8 6 4 8 0 05mH 100A C 146 90 77 99 155 132 132 16 8 8 4 1 0 035mH 150A C 146 90 77 99 155 132 132 16 8 8 4 1 0 025mH 200A B 180 100 90 107 182 160 150 16 8 8 9 8 0 015mH 300A D 230 120 104 130 230 220 210 25 14 12 19 0 013m...

Page 155: ...H 30A A 114 95 89 110 114 150 100 13 6 6 4 4 0 9mH 50A A 134 111 87 107 134 160 115 14 6 6 6 5 0 5mH 75A A 134 111 87 107 134 160 115 14 6 6 6 8 0 4mH 100A A 162 135 102 133 162 180 140 17 8 8 12 5 0 25mH 150A A 162 135 114 145 162 188 140 17 8 8 13 8 0 2mH 200A A 162 135 122 153 162 200 139 17 8 8 15 5 0 15mH 300A B 160 120 123 140 190 225 230 21 10 12 19 0 177mH 400A B 200 150 160 170 200 280 27...

Page 156: ... as the drive Recommending specification of EMC filter Select an EMC filter in accordance with the model number of drive to suppress drive s electromagnetic conduction interference 200V Series Drive model number EMC filter model number EMC filter rated current phase RM6F5 2001 FN3270H 10 44 10A 3ψ RM6F5 2002 FN3270H 10 44 10A 3ψ RM6F5 2003 FN3270H 20 44 20A 3ψ RM6F5 2005 FN3270H 20 44 20A 3ψ RM6F5...

Page 157: ...270H 65 34 65A 3ψ RM6F5 4050 FN3270H 80 35 80A 3ψ RM6F5 4060 FN3270H 100 35 100A 3ψ RM6F5 4075 FN3270H 150 99 150A 3ψ RM6F5 4100 FN3270H 200 99 200A 3ψ RM6F5 4125 FN3270H 200 99 200A 3ψ RM6F5 4150 FN3270H 250 99 250A 3ψ RM6F5 4175 FN3270H 320 99 320A 3ψ RM6F5 4200 FN3270H 320 99 320A 3ψ RM6F5 4250 FN3270H 400 99 400A 3ψ RM6F5 4300 FN3270H 600 99 600A 3ψ RM6F5 4350 FN3270H 600 99 600A 3ψ RM6F5 4420...

Page 158: ...d possible injuries Please be more cautions to the sharp parts 3 Wiring or inspection must be done by qualified professional technicians By installing the RFI filter s it can reduce the radio frequency interference generated by drive Because the RFI filter is constructed by ferrite core it is not related to the capacity and voltage of drive 1 Specification of product Applied Model RM6E1 Environmen...

Page 159: ... or the four core cable with ground wire cannot pass through RFI filter otherwise the filtration will be reduced 2 Install the RFI filter at the output site of the drive RFI U V W RFI Motor U V W Motor Ex 1 Ex 2 3 If the power cords are too thick to be winded pass the power cords through RFI filter directly and connect two or more RFI in series RFI Filter U T1 V T2 W T3 Motor EX 1 3 Recommend to u...

Page 160: ...Appendix D Zero Phase Radio Frequency Filter Selection 160 App E 4 Outline dimensions of RFI 01 unit mm 5 Outline dimensions of RFI 02 ψ7 160 7 130 86 37 1 4 180 85 32 unit mm ...

Page 161: ...lection of Motor 161 App E 6 Outline dimensions of RFI 03 211 130 R5 5 44 37 12 22 3 ψ9 42 3 230 2 47 130 54 176 unit mm 7 Outline dimensions of RFI 04 276 175 7 R5 54 63 46 12 22 3 ψ9 295 42 3 2 47 241 154 unit mm ...

Page 162: ... decreased as well as the motor temperature can be increased For the long time and low speed operation use the variable frequency motor with the independent cooling fan c Standard 3 phase induction motor NEMA B characteristics as follows d When the motor speed exceeds the rated speed 50 60HZ the torque will be decreased while the motor speed increasing e Check the motor insulation The standard req...

Page 163: ...he customer support for repair service of drive Insulation tester Drive Drive Insulation Impedance Measurement 2 Measure the motor insulation impedance a Remove the U T1 V T2 W T3 cables of motor from the drive before measuring the motor insulation impedance and then measure the motor insulation impedance including motor cables using the insulation tester with DC500V The motor insulation impedance...

Page 164: ...autotransformer for 30 minutes from 0 volt to the half of drive s rated voltage and then to apply drive rated voltage to charge the drive for another 30 minutes B When charging the internal capacitor of drive the wiring between autotransformer and terminals R L1 S L2 of drive is shown as below Autotransformer AC Power 0 375 125 Drive 500 Output terminal Input terminal 250 Connection diagram betwee...

Page 165: ...HL500 40 500W 40Ω 335 320 60 20 5 3 1100 Notes 1 When the braking is frequently applied please increase the resistor wattage and add the cooling fan to prevent the resistor from overheating 2 Aluminum case resistors have the better thermal performance Please select 1 2 times rated power resistor by using general wirewound type resistor 3 Please use the heat resistant wire for the brake resistor wi...

Page 166: ... 2002 105 RM6F5 2003 75 RM6F5 2005 40Ω MHL500 40 1 120 RM6F5 2007 20Ω MHL500 40 2 2pcs in parallel 145 RM6F5 2010 115 RM6F5 2015 85 RM6F5 2020 13 3Ω MHL500 40 3 3pcs in parallel 95 RM6F5 2025B 10Ω MHL500 40 4 4pcs in parallel 100 RM6F5 2030B 8Ω MHL500 40 5 5pcs in parallel 100 RM6F5 2040B 6 6Ω MHL500 40 6 6pcs in parallel 100 RM6F5 2050B 3 3Ω MHL500 40 12 12pcs in parallel 150 RM6F5 2060B 2 5Ω MHL...

Page 167: ...30 RM6F5 4010 80Ω MHL500 40 2 2pcs in parallel 105 RM6F5 4015 80 RM6F5 4020 40Ω MHL500 400 4 2pcs in parallel 2 sets in series total 4 pcs 120 RM6F5 4025 100 RM6F5 4030 27Ω MHL500 400 6 3pcs in parallel 2 sets in series total 6 pcs 120 RM6F5 4040B 20Ω MHL500 400 8 4pcs in parallel 2 sets in series total 8 pcs 130 RM6F5 4050B 100 RM6F5 4060B 13 3Ω MHL500 400 12 6pcs in parallel 2 sets in series tot...

Page 168: ... specification Approximate braking torque 10 ED Model number Model DBU6 Unit set Recommending combination Unit set RM6F5 4125 H200 1 MHL500 40 24 12000W 6 6 12pcs in parallel 2 sets in series 1 125 RM6F5 4150 105 RM6F5 4175 H300 1 MHL500 40 36 18000W 4 4 18pcs in parallel 2 sets in series 1 130 RM6F5 4200 105 RM6F5 4250 H400 1 MHL500 40 48 24000W 3 3 24pcs in parallel 2 sets in series 1 115 RM6F5 ...

Page 169: ...phase AC power source single phase terminal are R L1 S L2 Thermal Switch OHD3 100B AC Motor Figure 1 1 Use the thermal switch to protect the temperature of braking resistor and generate an external fault signal to the multi function terminal X4 to stop the drive when the braking resistor is overheating and interrupt the connection of magnet contactor MC by output terminals Ta2 Tc2 2 Set the multi ...

Page 170: ...Motor PE Braking Resistor option R L1 S L2 T L3 MC RELAY OFF ON MC MC AC220V AC220V RELAY DC24V DC0V Thermal Switch OHD3 100B OHD3 100B Figure 2 When the drive power is controlled by the magnet contactor MC use the thermal switch to control magnet contactor MC When the braking resistor is overheating the contactor MC is disconnected ...

Page 171: ...U T1 PR P N Main Circuit Terminal Control Terminal PE R L1 S L2 T L3 MC X4 External Fault COM Braking Resistor option Three phase AC power source single phase terminal are R L1 S L2 AC Motor P N RB1 RB2 MC DBU6 Thermal guard OHD3 100B Figure 1 1 Use the thermal switch to protect the temperature of braking resistor and generate an external fault signal to the multi function terminal X4 to stop the ...

Page 172: ...M R L1 S L2 T L3 W T3 V T2 PE U T1 PR P N AC Motor PE R L1 S L2 T L3 MC RELAY OFF ON MC MC AC220V AC220V RELAY DC24V DC0V OHD3 100B Figure 2 When the drive power is controlled by the magnet contactor MC use the thermal switch to control magnet contactor MC When the braking resistor is overheating the contactor MC is disconnected ...

Page 173: ...er and External Display a Remote controller KP 605 Two types of the remote controller Internal panel type and external panel type 1 Dimension of internal panel type consist of A 01 KP 605 unit mm 2 Dimension of external panel type consist of A 01 A 02 KP 605 R2 5 M4 4攻牙 ψ5 32 5 65 14 37 63 2 2 48 2 124 112 6 Unit mm ...

Page 174: ...Display 174 App I b External display DM 501 1 Outline dimensions 2 7 90 6 96 98 75 44 7 1 5 2 Unit mm Panel cutting dimension 93 45 48 2 Appearance of display panel 3 The standard length of 2 54 5P wires is 1 5 m and 3 m respectively Do not exceed this length ...

Page 175: ...5 2001 RM6F5 2005 RM6F5 4001 RM6F5 4007 螺絲M4 4 128 138 128 142 5 5 138 151 5 6 5 2 Ø 6 5 5 46 149 85 5 107 110 unit mm Model Number RM6F5 2007 RM6F5 2020 RM6F5 4010 RM6F5 4030 Internal cooling type External cooling type 2 ψ6 6 hole 2 ψ35 3 ψ23 3 ψ23 2 ψ35 2 ψ6 Supporting frame accessory Model A0006804 V1 1 8 hole unit mm ...

Page 176: ...133 252 25 3 235 445 ScrewM8 4 235 253 2 Ø 10 427 10 445 460 9 163 25 3 130 254 Panel cutting dimension unit mm Model Number RM6F5 2060 RM6F5 2250 RM6F5 4100 RM6F5 4700 Internal cooling type External cooling type H2 H1 H D2 d H1 W3 W W3 W1 h1 D0 D1 h2 H3 H4 D2 W4 W3 H H1 H2 d W1 W W3 h1 D0 D1 h2 2 ψ d hole 2 ψ d hole 4 screw 4 screw Panel cutting dimension Internal cooling type External cooling ty...

Page 177: ... d1 3 3 3 3 d 10 12 15 15 D2 242 246 257 294 D1 170 172 183 224 D0 325 334 366 405 h3 10 12 12 18 h2 25 30 35 39 h1 11 14 19 15 H4 545 634 758 936 H3 564 662 788 978 H2 539 630 751 929 H1 562 660 785 974 H 584 685 818 1000 W4 365 427 487 657 W3 275 275 275 580 W1 361 418 479 654 W 386 446 508 696 Model number RM6F5 2060B3 RM6F5 2075B3 RM6F5 2100B3 RM6F5 2125B3 RM6F5 2150B3 RM6F5 2200B3 RM6F5 2250B...

Page 178: ... 366 405 419 h3 10 12 12 18 19 h2 25 30 35 39 39 h1 11 14 19 15 15 H4 545 634 758 936 968 H3 564 662 788 978 1007 H2 539 630 751 929 963 H1 562 660 785 974 1003 H 584 685 818 1000 1030 W4 365 427 487 657 958 W3 275 275 275 580 710 W1 361 418 479 654 954 W 386 446 508 696 992 Model number RM6F5 4100B3 RM6F5 4125B3 RM6F5 4150B3 RM6F5 4175B3 RM6F5 4200B3 RM6F5 4250B3 RM6F5 4300B3 RM6F5 4350B3 RM6F5 4...

Page 179: ...Attachment 1 Dimension of Keypad 179 Att 1 Attachment 1 Dimension of Keypad KP 605 60 16 23 55 85 23 48 23x23 ψ30 2 M3 screw 96 1 0 66 1 0 Scale 1 1 Unit mm ...

Page 180: ...0 5 0 5 0 5 0 5 0 5 F_010 Starting Voltage 8 0 8 0 8 0 8 0 8 0 F_011 Base Frequency 60 0 60 0 60 0 50 0 60 0 F_012 Base Voltage 220 0 220 0 220 0 220 0 220 0 F_013 Selection of Pump Shift Operation Parallel control 3 3 3 3 3 F_015 Control Mode Selection Parallel control 0 1 2 1 5 F_016 Set Drive s No for Parallel Control 0 0 0 0 0 F_017 Maximum Output Frequency 60 0 60 0 60 0 50 0 60 0 F_018 Refer...

Page 181: ...0 30 00 30 00 30 00 F_035 Preset Speed 4 45 00 45 00 45 00 45 00 45 00 F_036 Preset Speed 5 50 00 50 00 50 00 50 00 50 00 F_037 Preset Speed 6 55 00 55 00 55 00 55 00 55 00 F_038 Preset Speed 7 60 00 60 00 60 00 50 00 60 00 F_039 Jog Speed 7 00 7 00 7 00 7 00 7 00 F_040 Vin Gain 1 00 1 00 1 00 1 00 1 00 F_041 Vin Bias 0 00 0 00 0 00 0 00 0 00 F_042 Frequency Upper Limit 1 00 1 00 1 00 1 00 1 00 F_...

Page 182: ... 0 0 0 0 0 0 F_064 Automatic Boost Voltage Range 1 0 1 0 1 0 1 0 1 0 F_065 System Overload Detection OLO 0 0 0 0 0 F_066 System Overload Detecting Selection 0 0 0 0 0 F_067 Output Setting after System Overload 0 0 0 0 0 F_068 System Overload Detection Level 160 160 160 160 160 F_069 System Overload Detection Time 2 0 2 0 2 0 2 0 2 0 F_070 Stall Prevention Level at Acceleration 170 170 170 170 170 ...

Page 183: ...ressure Boost for Water Usage Detection 0 15 0 15 0 15 0 15 0 15 F_085 Time Interval of Pressure Boost for Water Usage Detection 0 35 35 35 35 F_086 ON OFF Mode Starting Rate Setting 0 0 0 0 0 F_087 ON OFF Mode Pressure Dead Band Setting 0 3 0 3 0 3 0 3 0 3 F_088 The Current Level of Speed Tracing 150 150 150 150 150 F_089 Delay Time for Speed Tracing 0 5 0 5 0 5 0 5 0 5 F_090 The V F Pattern of S...

Page 184: ... Integration Upper Limitation 100 100 100 100 100 F_110 Integration Lower Limitation 0 0 0 0 0 F_111 PID Offset Adjustment 0 65 65 65 65 F_112 PID Buffer Space 2 2 2 2 2 F_113 Feedback Signal Filter 10 10 10 10 10 F_114 Feedback Signal Trip Detection 0 1 0 1 1 F_115 Acceleration Time of Pressure Boost 0 6 0 6 0 6 0 6 0 6 F_116 Parameter Selection 0 0 0 0 0 F_117 PID Start Range 0 3 0 3 0 3 0 3 0 3...

Page 185: ...Water Detection 0 10 0 10 10 F_134 Default Setting 10 10 10 10 10 F_135 Number of Drives Standing By 0 0 0 0 0 F_136 Noise Prevention 0 0 0 0 0 F_137 Delay Time at Pump Exchange Operation 0 0 0 0 0 F_138 200 Current Limit 0 0 0 0 0 F_139 Reserved 0 0 0 0 0 F_140 NTC Thermistor Setting 1 1 1 1 1 F_141 Drive Overheat Pre alarm Selection 0 0 0 0 0 F_142 Drive Overheat Pre alarm Level 70 70 70 70 70 F...

Page 186: ... 100 100 100 100 100 F_163 Frequency Lower Limitation by Manual Mode 0 0 0 0 0 F_166 K Value of Flow Sensor 10 0 10 0 10 0 10 0 10 0 F_167 Rate of Flow Sensor 1 00 1 00 1 00 1 00 1 00 F_168 Unit of Flow Sensor 0 0 0 0 0 F_171 Shutoff Head H 12 0 12 0 12 0 12 0 12 0 F_172 Maximum Flow Q 300 0 300 0 300 0 300 0 300 0 F_173 Compensation for Pipe Friction Loss 0 0 0 0 0 F_174 The Current in Maximum Fl...

Page 187: ...Sequential Operation F_185 Setting Sector 2 of Sequencial Operation F_186 Setting Sector of Sequencial Operation F_187 Setting Sector 4 of Sequencial Operation F_188 Setting Sector 5 of Sequencial Operation F_189 Setting Sector 6of Sequencial Operation F_190 Setting Sector 7 of Sequencial Operation F_191 Setting Sector 8 of Sequencial Operation F_193 Switching Frequency F_194 Default Setting 0 0 0...

Page 188: ... F_029 0 0 F_005 1 F_030 1 F_006 7 F_031 0 00 F_007 10 0 F_032 20 00 F_008 100 F_033 25 00 F_009 0 5 F_034 30 00 F_010 8 0 F_035 45 00 12 0 F_011 60 0 F_036 50 00 F_012 220 0 F_037 55 00 380 0 F_013 3 F_038 60 00 F_014 F_039 7 00 F_015 1 F_040 1 00 F_016 0 F_041 0 00 F_017 60 0 F_042 1 00 F_018 60 00 F_043 0 00 F_019 1 0 F_044 0 F_020 1 0 F_045 1 00 F_021 6 0 F_046 1 F_022 0 4 F_047 20 F_023 50 0 ...

Page 189: ...F_078 0 F_054 1 F_079 1 F_055 2 F_080 10 F_056 F_081 6 F_057 F_082 0 F_058 1 F_083 6 F_059 2 F_084 0 15 F_060 11 F_085 35 F_061 3 F_086 0 F_062 2 0 F_087 0 3 F_063 0 0 F_088 150 F_064 1 0 F_089 0 5 F_065 0 F_090 100 F_066 0 F_091 F_067 0 F_092 0 F_068 160 F_093 1 F_069 2 0 F_094 1 F_070 140 F_095 220 0 200V系列 F_071 130 380 0 400V系列 F_072 3 0 F_096 0 00 F_073 3 0 F_097 10 F_098 1 F_098 1 ...

Page 190: ... F_133 10 F_105 3 0 F_134 0 F_106 1 2 F_135 0 F_107 0 00 F_136 0 F_108 0 00 F_137 10 F_109 100 F_138 0 F_110 0 F_139 F_111 65 F_140 0 F_112 2 F_141 0 F_113 10 F_142 70 F_114 1 F_143 3 0 F_115 0 6 F_144 1 F_116 0 F_145 50 F_117 0 3 F_146 0 5 F_118 1 F_147 0 F_119 40 F_148 100 F_120 0 F_149 2 0 F_121 60 F_150 0 F_122 5 F_155 0 F_123 0 F_156 1 F_124 0 F_157 1 F_125 1 F_158 0 0 F_126 0 F_159 0 F_127 1...

Page 191: ... Memo 191 Att 3 Func Description dEF50 Setting Value Func Description dEF50 Setting Value F_162 100 F_174 100 F_163 0 F_175 30 F_166 10 0 F_176 0 0 F_167 1 00 F_177 40 F_168 0 F_180 0 F_171 12 0 F_183 0 F_172 300 0 F_194 0 ...

Page 192: ... Motor overload LE1 SV KEYPAD PV Running Under voltage during operation OL1 SV KEYPAD PV Running Drive overload OC SV KEYPAD PV Running Drive over current OLO SV KEYPAD PV Running System overload GF SV KEYPAD PV Running Grounding fault thr SV KEYPAD PV Running External fault OP SV KEYPAD PV Running Over pressure ntCF SV KEYPAD PV Running NTC Thermistor sensor fault OE SV KEYPAD 設定值 PV 實際值 Running ...

Page 193: ...e output interruption Err_00 SV KEYPAD PV Running Err_01 SV KEYPAD PV Running Err_00 Keypad cable trip before connecting Err_01 Keypad cable trip during operation Fr SV KEYPAD PV Running Coast to stop dtF SV KEYPAD PV Running Direction command error db SV KEYPAD PV Running Dynamic brake transistor over voltage Wr_F SV KEYPAD PV Running Different software version inter copy PrEr SV KEYPAD PV Runnin...

Page 194: ...Notes 194 Notes ...

Page 195: ...Notes 195 Notes ...