Page 471 of 485
Error Source
Code
Category Error Message
Possible Cause
Resolution
Front panel
Fault
333
Error
Node in non-operational
mode. Run unit discovery
to recover.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
Fault
334
Error
Power failure.
Check AC input voltage. If
error persists, contact
customer service
Front panel
Fault
335
Error
Remote inhibit was issued
from remote interface.
Setting conflict. Remote
inhibit conflicts with
Output state
Check Remote inhibit
mode setting and
connections
Front panel
Fault
336
Error
System about to reboot.
Notification. Reboot
imminent. Normal after
completing front panel
firmware update
Wait for all firmware
updates to be completed
Front panel
Fault
337
Error
Missed node.
An inconsistency was
detected in the power
source's internal
communication network.
Try recycling power. If
error persists, contact
customer service
Front panel
Fault
338
Error
One or more inverters did
not get enabled.
Failed to enable one or
more output power
stages
Try recycling power. If
error persists, contact
customer service
Front panel
Fault
339
Error
One or more primaries
did not get enabled.
Failed to enable one or
more input power stages
Try recycling power. If
error persists, contact
customer service
Front panel
Fault
340
Error
Firmware version
mismatch
Firmware Error. Power
stage firmware version is
older than expected
Check for correct
firmware image file and
version.
Front panel
Fault
341
Error
Firmware version
mismatch. Front panel
version is older than
expected. Contact
technical support.
Firmware Error. Front
panel firmware version is
older than expected
Check for correct
firmware image file and
version.
Front panel
Fault
342
Error
Mismatch between
hardware revisions of
units in parallel.
Error during discovery.
Not all paralleled units
are of same hardware
revision
Contact customer service
Front panel
Fault
343
Error
Power stage firmware
update failed.
Send command:
SYSTem:FW:POWER:UPD
ATE:STAT? for more
information
Run unit discovery to
recover.
Front panel
Fault
344
Error
Firmware update was
interrupted
Recovery is needed
Front panel
Fault
345
Error
GPIB hardware not found
in this unit.
Configuration Error. GPIB
Interface option not
found
Check model type tag for
installed options
Front panel
Fault
346
Error
GPIB hardware detected
Configuration Error. GPIB
Interface found but not
configured
Check model type tag for
installed options
Front panel
Fault
347
Error
IO hardware not found in
this unit.
Configuration Error. Aux
I/O hardware missing
Check model type tag for
installed options
Front panel
Fault
348
Error
IO hardware detected
Configuration Error. Aux
I/O hardware found but
not configured
Check model type tag for
installed options
Summary of Contents for AFX Series