AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 220 of 485
8.4
Measurement Commands
Measurement commands are typically queries only and return power source measurement
data values. This section is broken down into the commands for each measurement
parameter.
The following measurement commands are supported.
8.4.1
Voltage Measurement Commands
Query Format
MEASure:VOLTage[:ACDC]#?
Description
Returns the measured RMS voltage for the selected phase #. If no
phase number is specified, returns the reading for all phases.
Returned Data Format
<nr2>
Query Example
MEAS:VOLT:ACDC2?
230.0000
Query Format
MEASure:VOLTage:DC#?
Description
Returns the measured DC voltage for the selected phase #. If no
phase number is specified, returns the reading for all phases.
Returned Data Format
<nr2>
Query Example
MEAS:VOLT:DC1?
2.2500
Query Format
MEASure:VOLTage:AC#?
Description
Returns the measured RMS voltage for the selected phase #. If no
phase number is specified, returns the reading for all phases. This
command is equivalent to “MEASure:VOLTage[:ACDC]#?” and is
provided for backward compatibility with the UPC controllers.
Returned Data Format
<nr2>
Query Example
MEAS:VOLT:AC3?
230.0000
Query Format
MEASure:VLL#?
Description
Returns the measured RMS Line-to-Line voltage
1
for the selected
phase #. If no phase number is specified, returns the reading for all
phases. Phase reference applies as follows:
# = 1 V
AB
, # = 2 V
AC
, # =3 V
BC
Returned Data Format
Query Example
MEAS:VLL2?
398.3780
Note 1:
Line to Line voltage measurements are calculated based on VLN and phase angles and are
valid only for sinusoidal voltage waveforms with low levels of distortion and under balanced three
phase load conditions.
Summary of Contents for AFX Series
Page 484: ......