AFX SERIES® OPERATION MANUAL
SECTION 13:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 467 of 485
Error Source
Code
Category Error Message
Possible Cause
Resolution
Primary Fault
212
Error
AC input: voltage is below
minimum.
Primary Fault
213
Error
AC input: missing phase.
Primary Fault
214
Error
PFC DC bus voltage
regulation lost.
Primary Fault
215
Error
PFC DC bus voltage limit
exceeded. CLA OVP Trip
Primary Fault
216
Error
Temperature 1 protection
(input stage)
AC Input Stage heatsink
temperature exceeded
maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
217
Error
Temperature 1 protection
(input stage)
AC Input Stage heatsink
temperature exceeded
maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
218
Error
Temperature 2 protection
(PFC/LLC)
PFC and DC/DC Converter
heatsink temperature
exceeds maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
219
Error
Temperature 2 protection
(PFC/LLC)
PFC and DC/DC Converter
heatsink temperature
exceeds maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
220
Error
Temperature 3 protection
(PFC/LLC)
PFC and DC/DC Converter
heatsink temperature
exceeds maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
221
Error
Temperature 3 protection
(PFC/LLC) exceeded
minimum limit.
PFC and DC/DC Converter
heatsink temperature
exceeds minimum limit.
Primary Fault
222
Error
Temperature 4 protection
(main transformer)
High Frequency
Transformer temperature
exceeds maximum limit.
Check for possible air
flow obstructions and
ambient temperature
Primary Fault
223
Error
Temperature 4 protection
(main transformer)
High Frequency
Transformer temperature
exceeds minimum limit.
Primary Fault
224
Error
Internal bias supply fault. Internal Bias Supply fault
occurred
Check for correct AC
input voltage connection.
Primary Fault
226
Error
Hardware does not match
input voltage setting.
Incorrect AC input voltage
detected
Check for correct AC
input voltage rating.
Primary Fault
227
Error
Primary capacitor board
not detected.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cables if they
exist, and then turn unit
on. If problem recurs
contact customer service.
Primary Fault
228
Error
Invalid node ID. Run unit
discovery to recover.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cables if they
exist, and then turn unit
on. If problem recurs
contact customer service.
Primary Fault
229
Error
Incorrect DSP type
detected. Cycle-power to
re-try.
Unable to detect correct
DSP type.
Try cycling AC input
power.
Primary Fault
230
Error
PFC output current peak
protection.
PCF stage output current
exceeded maximum peak
level.
Possible overload on one
or more output inverters.
Primary Fault
231
Error
PFC output current slow
protection
Primary Fault
232
Error
AC input: voltage is above
maximum.
Incorrect AC input voltage
detected
Check for correct AC
input voltage rating.