AFX SERIES® OPERATION MANUAL
SECTION 13:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 460 of 485
Error Source
Code
Category Error Message
Possible Cause
Resolution
Front panel
Error
64
Error
Unexpected reset.
Inverter controllers were
reset
Try recycling power. If
error persists, contact
customer service
Front panel
Error
65
Error
Front panel is in passive
mode.
Passive Mode. Front
panel is most likely an
auxiliary unit
Check parallel
configuration
Front panel
Error
66
Error
Invalid host name.
Host name requested is
invalid
Try recycling power. If
error persists, contact
customer service
Front panel
Error
67
Error
DC voltage set point
cannot change due to
waveform saturation.
Setting conflict.
Waveform data and DC
setting or in conflict
Adjust DC setting or
waveform to resolve
conflict
Front panel
Error
68
Error
AC voltage set point
cannot change due to
waveform saturation.
Setting conflict.
Waveform data and AC
setting or in conflict
Adjust AC setting or
waveform to resolve
conflict
Front panel
Error
69
Error
Maximum user limit is
lower than set point.
Setting conflict. Set point
exceeds upper user limit
Adjust setting or user
limit
Front panel
Error
70
Error
Minimum user limit is
higher than set point.
Setting conflict. Set point
is below lower user limit
Adjust setting or user
limit
Front panel
Error
71
Error
Set point reduced due to
low range.
Setting conflict. Set point
exceeds low voltage
range setting
Select High Range or
lower set point
Front panel
Error
72
Error
Minimum limit is higher
than maximum.
Setting conflict. Max.
User Limit must be higher
than Min. User Limit
Adjust User Limits
Front panel
Error
73
Error
Maximum limit is lower
than minimum.
Setting conflict. Max.
User Limit must be higher
than Min. User Limit
Adjust User Limits
Front panel
Error
74
Error
Waveform description is
not available.
No Waveform Alias name
provided
Assign Alias name to
waveform
Front panel
Error
75
Error
IP address conflict. May
be duplicated.
Duplicate IP detected
Check IP or renew lease
Front panel
Error
76
Error
Invalid filename.
File name invalid
Check file name
Front panel
Error
77
Error
External memory storage
is not available.
Can't find external
memory device selected.
External storage device
selected may have been
removed
Re-insert external
memory device or select
different memory type
Front panel
Error
78
Error
Data logger rate not
allowed.
Data logging rate set is
invalid
Adjust logging rate
setting
Front panel
Error
79
Event
Data logger is running
Trying to change
configuration settings
while data logging is in
progress. Stop data
logger function before
changing configuration
Stop data logger function
before changing
configuration
Front panel
Error
80
Error
Data logger execution
error.
Error during data logging
Stop data logger function
Front panel
Error
84
Event
Unable to change form
while output is enabled.
Trying to change phase
mode while output is ON.
Phase mode (FORM)
cannot be changed while
output is ON
Turn output OFF first,
then change FORM
Front panel
Error
85
Error
Unable to clear one or
more fault.
Could not clear one or
more faults when
requested
Try recycling power. If
error persists, contact
customer service