AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 329 of 485
Query Syntax
[SOURce:]PULSe:PHASe#:MINimum?
Description
This command returns the minimum permissible set value of the
initial PULSE phase angle for selected phase #
Returned Data Format
<nr1>
Query Example
PULS:PHAS1:MIN?
0.0000
Query Syntax
[SOURce:]PULSe:PHASe#:MAXimum?
Description
This command returns the maximum permissible set value of the
initial PULSE phase angle for selected phase #
Returned Data Format
<nr1>
Query Example
PULS:PHAS1:MAX?
360.000
Query Syntax
[SOURce:]PULSe:PHASe#:DEF?
Description
This command returns the default set value of the initial PULSE phase
angle for selected phase #
Returned Data Format
<nr1>
Query Example
PULS:PHAS2:DEF?
120.0000
PULS:PHAS3:DEF?
240.0000
Command Syntax
[SOURce:]PULSe <cr>
>>> Alias for PROGram:TRANsient command. <<<
Description
This command controls pulse transient execution
Parameters
< RUN | STOP | PAUSe | STEP | RESTart >
Parameter Format
<cr>
Example
PULS RUN
Query Format
[SOURce:]PULSe?
Description
Query format returns the pulse transient execution state as either
RUN, STOP, PAUS, STEP or REST
Returned Data Format
<nr1>
Return values respresent running state as follows:
0
Stopped
1
Running
2
Paused
3
Stepping
4
Waiting for trigger
Query Example
PULS?
1
Summary of Contents for AFX Series
Page 484: ......