Comparison of the CX-Simulator and SYSMAC CS/CJ-series PLCs
Section 1-6
23
Item CS/CJ-series
PLC
CX-Simulator
Periph-
eral port
Host Link, peripheral bus, NT Link (1:N), (Pro-
gramming Console and peripheral bus are
automatically recognized.)
(No-protocol is not possible for the peripheral
port.)
The peripheral port is not sup-
ported.
RS-232C
port
Host Link, peripheral bus, NT Link (1:N), and
No-protocol.
(1:1 links and peripheral bus are not supported
for the RS-232C port.)
Host Link, No-protocol, and NT
Link are supported.
Mode
USB port Peripheral bus, EtherNet/IP (CJ2-series PLCs
only)
The USB port is not supported.
Periph-
eral port
The peripheral port is not sup-
ported.
Serial com-
munications
(peripheral
port or
RS-232C
ports)
Baud
rate
RS-232C
port
300/600/1,200/2,400/4,800/9,600/19,200/
38,400/57,600/115,200 bps
(Baud rates of 38,400/57,600/115,200 bps are
not standard for RS-232C.)
Same as shown at left.
(The actual speed will vary de-
pending on the hardware of the
computer.)
Network communications timing
Performed as peripheral servicing.
When in Continuous Run, per-
formed as peripheral servicing.
When in pausing, the network
communications processing is
performed.
Interrupt control modes
If an interrupt occurs during Host Link servicing,
Remote I/O servicing, Special I/O Unit servicing,
or execution of an instruction, that process will be
stopped immediately and the task will be exe-
cuted instead.
Interrupt is prohibited during pe-
ripheral servicing and execution of
an instruction.
Startup mode
The CS/CJ-series CPU Unit will start in
PROGRAM mode if the Startup Mode is set in
the PLC Setup to PRCH: Switch Setting on
Programming Console (default setting) and the
CPU Unit is started without a Programming
Console connected.
Only "PRCH: Switch Setting on
Programming Console" (default
setting) (Will start in PROGRAM
mode as a Programming Console
is not connected.)
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......