![background image](http://html1.mh-extra.com/html/omron/cx-simulator-1-9/cx-simulator-1-9_operation-manual_744207258.webp)
I/O Memory Allocation
Section 9-3
219
Address CS/CJ-series
PLC
CX-Simulator
Words Bits
Name
Function Settings
Function
Settings
A400
All
Error code When a non-fatal error
(user-defined FALS(006) or sys-
tem error) or a fatal error
(user-defined FALS(007) or sys-
tem error) occurs, the 4-digit
hexadecimal error code is written
to this word. When two or more
errors occur simultaneously, the
highest error code will be re-
corded.
Refer to the
CS/CJ Series Op-
eration Manual
for details on error
codes.
Error code Same as
CS/CJ-series
PLC.
A40103 Card
Transfer
Error Flag
ON when the contents of the
memory card cannot be trans-
ferred to the CPU Unit at power
ON. (CJ2-series PLCs only)
Not used.
A40105 Version
Error Flag
ON when the transferred user
program contains a function that
is not supported by the unit ver-
sion of the CPU Unit. (CJ2-series
PLCs only)
0: No error
1: Error
Not used.
A40106 FALS
Error
Flag (Fatal
error)
ON when a non-fatal error is
generated by the FALS(006)
instruction. The CPU Unit will
continue operating and the
ERR/ALM indicator will flash.
The corresponding error code will
be written to A400. Error codes
C101 to C2FF correspond to
FALS numbers 001 to 511.
This flag will be turned OFF when
the FALS errors are cleared.
1:
FALS(006)
executed
0:
FALS(006)
not exe-
cuted
Same as
CS/CJ-series
PLC.
A401
A40108 Cycle
Time
Too Long
Flag
(Fatal error)
ON if the cycle time exceeds the
maximum cycle time set in the
PLC Setup (the cycle time moni-
toring time). CPU Unit operation
will stop and the ERR/ALM indi-
cator on the front of the CPU Unit
will light.
This flag will be turned OFF when
the error is cleared.
0: Cycle
time under
max.
1: Cycle
time over
max.
Same as
CS/CJ-series
PLC.
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......