![background image](http://html1.mh-extra.com/html/omron/cx-simulator-1-9/cx-simulator-1-9_operation-manual_744207263.webp)
I/O Memory Allocation
Section 9-3
224
Address CS/CJ-series
PLC
CX-Simulator
Words Bits
Name
Function Settings
Function
Settings
A40213 Interrupt
Task Error
Flag
(Non-fatal
error)
ON when the Detect Interrupt
Task Errors setting in the PLC
Setup is set to “Detect”
and an
interrupt task is executed for
more than 10 ms during I/O re-
freshing of a C200H Special I/O
Unit or a SYSMAC BUS I/O Unit.
This flag will also be turned ON if
an attempt is made to refresh a
Special I/O Unit’s I/O from an
interrupt task with IORF(097)
while the Unit’s I/O is being re-
freshed by cyclic I/O refresh-
ing(duplicate refreshing).
1: Interrupt
task error
0: No error
Not used.
A402
A40215 FAL
Error
Flag
(Non-fatal
error)
ON when a non-fatal error is
generated by executing
FAL(006). The CPU Unit will
continue operating and the
ERR/ALM indicator on the front of
the CPU Unit will flash.
The bit in A360 to A391 that cor-
responds to the FAL number
specified in FALS(006) will be
turned ON and the corresponding
error code will be written to A400.
Error codes 4101 to 42FF cor-
respond to FAL numbers 001 to
2FF (0 to 511).
(This flag will be turned OFF
when the error is cleared.)
1:
FALS(006)
error oc-
curred
0:
FALS(006)
not exe-
cuted
Same as
CS/CJ-series
PLC.
A403 A40300
to
A40308
Memory
Error Loca-
tion
When a memory error occurs, the
Memory Error Flag (A40115) is
turned ON and one of the fol-
lowing flags is turned ON to in-
dicate the memory area where
the error occurred
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CS/CJ-series CPU Bus
Unit Settings
When a memory error occurs, the
CPU Unit will continue operating
and the ERR/ALM indicator on
the front of the CPU Unit will
flash.
(The corresponding flag will be
turned OFF when the error is
cleared.)
1: Error
0: No error
Same as
CS/CJ-series
PLC.
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......