I/O Memory Allocation
Section 9-3
227
Address CS/CJ-series
PLC
CX-Simulator
Words Bits
Name
Function Settings
Function
Settings
A40800
to
A40807
Basic I/O Unit
Error, Slot
Number
When an error has occurred in a
Basic I/O Unit (including C200H
Group-2 High-density I/O Units
and C200H Interrupt Input
Units), A40212 will be turned
ON and the slot number where
the error occurred will be written
here in binary.
00 to 09
hexadecimal
(Slots 0 to 9)
Not used.
A408
A40808
to
A40815
Basic I/O Unit
Error, Rack
Number
When an error has occurred in a
Basic I/O Unit (including C200H
Group-2 High-density I/O Units
and C200H Interrupt Input
Units), A40212 will be turned
ON and the Rack number where
the error occurred will be written
here in binary.
00 to 07
hexadecimal
(Racks 0 to 7)
Not used.
A409 A40900
to
A40907
Expansion I/O
Rack Number
Duplication
Flags
The corresponding flag will be
turned ON when an Expansion
I/O Rack’s starting word address
was set from a Programming
Device and two Racks have
overlapping word allocations or
a Rack’s starting address ex-
ceeds CIO 0901. Bits 00 to 07
correspond to Racks 0 to 7.
1: Error
0: No error
Not used.
A410 A41000
to
A41015
CS/CJ-series
CPU Bus Unit
Number Du-
plication
Flags
The Duplication Error Flag
(A40113) and the corresponding
flag in A410 will be turned ON
when a CS/CJ-series CPU Bus
Unit’s unit number has been
duplicated. Bits 00 to 15 corre-
spond to unit numbers 0 to F.
CPU Unit operation will stop and
the ERR/ALM indicator on the
front of the CPU Unit will light.
1: Duplication
detected
0: No duplica-
tion
Not used.
A411 to
A416
A41100
to
A41615
Special I/O
Unit Number
Duplication
Flags
The Duplication Error Flag
(A40113) and the corresponding
flag in A411 through A416 will
be turned ON when a Special
I/O Unit’s unit number has been
duplicated.
1: Duplication
detected
0: No duplica-
tion
Not used.
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......