Serial Communications Connection
Section 5-3
128
5-3-2 Access to External Device Using Serial Communications
Slave initiation via Host Link (FINS communications)
When performing FINS communications via Host Link by a ladder program,
external communications from a computer are not restricted, which is different
from the case of FINS communications for a network (communications via a
Network Communications Unit). (Network communications are restricted
within the local computer. Refer to
6-1 Outline of Network Communications
for
details.) Thus the slave initiation function can be checked by connecting the
COM port on the computer to another computer.
Access via No-protocol
No-protocol communications are available for connecting a barcode reader,
etc., allowing to process data read from a barcode reader in more practical
way.
5-3-3 Precautions in Using Serial Communications
Using Programmable Terminal via NT Link
Even when connecting a PT via NT Link, the Programming Console function
and Device Monitoring function are not available. In addition, use a PT with a
version of NT31/631-V2 or higher. When connecting a PT with the previous
version, select Host Link as the communications protocol.
FINS Command addressed to Serial Port
In the CX-Simulator’s FINS communications, only a command addressed to
the CPU Unit is accepted. FINS communications addressed to the serial port
of individual Ladder Engines are not available.
Changing Communications Protocol during [Work CX-Simulator]
When the communications protocol has been changed by the
CX-Programmer’s PLC Setup settings, etc., be sure to once [Disconnect] and
then [Connect] again. The newly set protocol becomes effective after the
[Connect].
Program
Slave
initiation
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......