I/O Memory Allocation
Section 9-3
223
Address CS/CJ-series
PLC
CX-Simulator
Words Bits
Name
Function Settings
Function
Settings
A40207 CS/CJ-series
CPU Bus Unit
Error Flag
(Non-fatal
error)
ON when an error occurs in a
data exchange between the CPU
Unit and a CS/CJ-series CPU
Bus Unit (including an error in the
CS/CJ-series CPU Bus Unit it-
self).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The CS/CJ-series CPU Bus
Unit where the error occurred will
stop operating and the unit
number of the Unit where the
data exchange error occurred is
indicated in A417.
(This flag will be turned OFF
when the error is cleared.)
1: Error in
one or more
Units
0: No error
in any Unit
Not used.
A40208 Inner
Board
Error Flag
(Non-fatal
error)
ON when an error occurs in a
data exchange between the CPU
Unit and the Inner Board (in-
cluding an error in the Inner
Board itself).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The Inner Board will stop
operating and details on the error
will be written to A424.
(This flag will be turned OFF
when the error is cleared.)
1: Error
0: No error
Not used.
A40209 I/O
Verifica-
tion Error Flag
(Non-fatal
error)
ON when a Basic I/O Unit regis-
tered in the I/O Table does not
match the Basic I/O Unit actually
installed in the PLC because a
Unit was added or removed.
1: Mis-
match
0: No mis-
match
Not used.
A40210 PLC
Setup
Error Flag
(Non-fatal
error)
ON when there is a setting error
in the PLC Setup. The CPU Unit
will continue operating and the
ERR/ALM indicator on the front of
the CPU Unit will flash.
The location of the error will be
written to A406.
(This flag will be turned OFF
when the error is cleared.)
1: Error
0: No error
Same as
CS/CJ-
series PLC.
A402
A40212 Basic I/O Unit
Error Flag
(Non-fatal
error)
ON when an error has occurred in
a Basic I/O Unit (including C200H
Group-2 High-density I/O Units
and C200H Interrupt Input Units).
1: Error
0: No error
Not used.
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......