Connecting PT via NT Link
Section 5-4
130
5-4 Connecting PT via NT Link
The diagram below illustrates how to connect OMRON’s Programmable Ter-
minal (PT) via NT Link.
1,2,3…
1. Set to NT Link (1:N) the communications protocol setting for the Ladder
Engine’s port used by the CX-Programmer.
Note
Only the RS-232C port of the CPU Unit (Unit No.: 00H) can be changed using
the CX-Programmer’s PLC Setup setting. Otherwise, directly change the
corresponding DM values from the PLC memory window, etc.
2. Once [Disconnect].
3. Select [Status] | [Settings] | [Serial communications settings] to display
[Serial communications settings] window.
4. Select the Serial port of the Serial Communications Unit to be used, fol-
lowed by pressing the [Edit] button to display [Serial communications reg-
istration] window.
5. Set the Communications Setting to [Actual communications] to select a
COM port name.
Note
Do not select a COM port name that overlaps with the one allocated in actual
communications or the Serial Data File.
6. Press the [OK] button to exit the [Serial communications registration]
window and to return to the [Serial communications settings] window.
7. Confirm the communications settings and the COM port name are identical
to the contents set in procedure 5 to press the [OK] button.
8. Download the screen data to the PT. For the communications settings on
the PT, set as Protocol: NT Link (1:N), Unit No.: 0, Communications speed:
Standard.
Note
If a COM port used by the PT’s support tool overlaps with the one used by the
CX-Simulator, downloading may fail in the [Connect] status. After [Discon-
nect], download by the support tool.
9. After completing setting on the PT, [Connect] to perform actual commu-
nications via NT Link.
Note
In the NT Link communications, I/O memory values are read/written from/to
the PT halfway during the Ladder Engine’s scanning because the communi-
cations are executed asynchronously to the Ladder Engine.
PT
PT
Summary of Contents for CX-Simulator 1.9
Page 1: ...Cat No W366 E1 10 CX Simulator Ver 1 9 SYSMAC WS02 SIMC1 E OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 SIMC1 E CX Simulator Ver 1 9 Operation Manual Revised December 2009...
Page 24: ...xxv...
Page 30: ...xxxi...
Page 35: ...xxxvi...
Page 39: ......
Page 63: ...Comparison of the CX Simulator and SYSMAC CS CJ series PLCs Section 1 6 24...
Page 75: ...Installing and Uninstalling the Software Section 2 1 36...
Page 157: ...Task Debugging Section 4 4 118...
Page 195: ...Connection with Application Programs Section 7 2 156...
Page 225: ...Checking the Result Section 8 5 186...
Page 277: ...Other Functions Section 9 4 238...
Page 289: ...Other Tips for Troubleshooting Section 10 3 250...
Page 304: ......
Page 305: ......