10. Specifications
PROGRAMMABLE AC/DC POWER SOURCE
246
10.27 External Interface
This is the interface to control the product from an external computer. The RS232 and USB
interfaces are provided by default, and either GPIB or LAN interface can be chosen when ordering.
(Both GPIB and LAN cannot be chosen.)
The command language is compliant with the SCPI Specification Version 1999.0. (Factory default
is USB).
USB interface (USB1.1) *43
Item
Description
Device class
USBTMC
ID
Already assigned for each device
Terminator “LF”
*43: The use of USB hub may cause a communication failure. It is recommended to use a
fully-shielded, short cable.
RS232 interface *44 *45
Item
Description or Selection
Factory default
Terminal
D-sub 9-pin (male, UNC #4-40 screw)
Baud rate
9600 / 19200
9600 bps
Terminator
“CR” “LF” / “CR” / “LF”
“CR” “LF”
Parity None/Odd/Even
None
Stop bit
1 / 2
1 bit
Data bit
7 / 8
8 bit
Flow control
None/Hardware/Software
None
*44: Binary transmission is not supported.
*45: Use a cross cable.
GPIB interface (IEEE488.1 std 1987) *46 *47
Item
Description or Selection
Factory default
Address
0 to 30
2
Terminator “LF”
*46: Binary transmission is not supported.
*47: Query for the main unit status byte using a serial poll is not supported.
LAN interface (IEEE802.3, LXI 1.4 Core 2011) *48
Item
Description or Selection
Factory default
Terminal RJ-45
modular
jack
Transmission method
Ethernet(100BASE-TX / 10BASE-T)
Communication protocol
SCPI-RAW
Terminator “LF”
IP address setting
Auto, Fixed
Auto
*48: Binary transmission is not supported.
Summary of Contents for KP3000GS
Page 1: ...PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Page 2: ......
Page 3: ...DA00033845 005 PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Page 4: ......
Page 5: ......
Page 19: ......
Page 20: ...KP3000GS 1 1 Outline 1 1 Overview 2 1 2 Features 2...
Page 23: ......
Page 197: ......
Page 207: ......
Page 219: ......
Page 243: ......
Page 275: ......
Page 277: ......
Page 278: ......