2. Preparation before Use
PROGRAMMABLE AC/DC POWER SOURCE
10
2.4
Grounding and Power Connections
Ensure to ground.
This product uses a line filter. If the product is not grounded, an electric shock might occur.
Ensure to connect the protective conductor terminal of the power input terminal of this product
to an earth ground so that ground resistance is 100
or less. If the product is not certainly
grounded, an electric shock might occur.
To prevent electric shock, ensure that the protective grounding conductor is connected before
you connect a cable to the power input terminals L and N.
For grounding, use the supplied power cable or an equivalent cable whose diameter is same or
greater (see Table 2-5).
Before connecting the product to power source, check the followings.
The power supply for this product must be taken from the distribution board.
Before connecting this product to the distribution board, be sure to cut the power to the
distribution board. Otherwise, an electric shock might occur.
Route the wire so that the distance between this product and the distribution board switch
(breaker) is 3 m or less. If the distance with the distribution board exceeds 3 m, install another
switch within 3 m from this product to connect. Use a switch complying with IEC 60947-1 and
IEC 60947-3 which can shut the power input from both L and N (excluding protective
grounding). Mark the switch with a sign indicating that it is a disconnecting device of power
input for KP3000GS.
These are from requirements in IEC 61010-1.
Condensation may form inside the product when the ambient temperature or humidity changes
suddenly, for example, after transportation in winter. In such case, leave the product in room
temperature enough time to evaporate the condensation, and then connect the product to the
power source.
Check the power source
For safety, use the product in the ranges of input voltage and frequency described below. Connect
the product to a distribution board which provides the power sufficiently higher than the maximum
input power (see Table 2-5).
Voltage range: Single-phase 100 to 230 V
Frequency range: 50 Hz/60 Hz
WARNING
WARNING
CAUTION
Summary of Contents for KP3000GS
Page 1: ...PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Page 2: ......
Page 3: ...DA00033845 005 PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Page 4: ......
Page 5: ......
Page 19: ......
Page 20: ...KP3000GS 1 1 Outline 1 1 Overview 2 1 2 Features 2...
Page 23: ......
Page 197: ......
Page 207: ......
Page 219: ......
Page 243: ......
Page 275: ......
Page 277: ......
Page 278: ......