544
14 TROUBLESHOOTING
14.5 List of Error Codes
1AB6H
Deceleration
time 3 setting
error
A value outside the setting range is set in [Pr.30] Deceleration
time 3 of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
■
During operation
The operation stops according to the setting of [Pr.39] Stop
group 3 sudden stop selection of detailed parameter 2
(deceleration stop/sudden stop). (for manual pulse generator
operation, deceleration stop only)
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 400 [Pr.28] Deceleration time 1 to [Pr.30]
1AB7H
JOG speed limit
value error
A value outside the setting range is set in [Pr.31] JOG speed
limit value of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 401 [Pr.31] JOG speed limit value.
1AB8H
A value set in [Pr.31] JOG speed limit value of detailed
parameter 2 is over [Pr.8] Speed limit value.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value so that [Pr.31] JOG speed limit value is
equal to or below [Pr.8] Speed limit value, and turn on PLC
READY signal [Y0] if the signal is off.
For details, refer to the following.
Page 389 [Pr.8] Speed limit value
Page 401 [Pr.31] JOG speed limit value
1AB9H
The value set in [Pr.31] JOG speed limit value of detailed
parameter 2 is below [Pr.7] Bias speed at start.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value so that [Pr.31] JOG speed limit value is
equal to or over [Pr.7] Bias speed at start, and turn on PLC
READY signal [Y0] if the signal is off.
For details, refer to the following.
Page 389 [Pr.8] Speed limit value
Page 401 [Pr.31] JOG speed limit value
1ABCH
JOG
acceleration
time selection
setting error
A value outside the setting range is set in [Pr.32] JOG
operation acceleration time selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 401 [Pr.32] JOG operation acceleration time
1ABDH
JOG
deceleration
time selection
setting error
A value outside the setting range is set in [Pr.33] JOG
operation deceleration time selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 402 [Pr.33] JOG operation deceleration time
1ABEH
Acceleration/
deceleration
processing
selection setting
error
A value outside the setting range is set in [Pr.34] Acceleration/
deceleration processing selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 402 [Pr.34] Acceleration/deceleration processing
1ABFH
S-curve ratio
setting error
A value outside the setting range is set in [Pr.35] S-curve ratio
of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 403 [Pr.35] S-curve ratio.
Error
code
Error name
Cause and description
Action
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......