7 CONTROL SUB FUNCTIONS
7.5 Functions that Change Control Details
Setting method
The following shows the data setting and a program example for setting the override value of the axis 1 to 200%.
• Set the following data.
For details on the settings, refer to the following.
Page 473 [Cd.13] Positioning operation speed override
• The following shows the time chart of the speed change using the override function.
• Add the following program to the control program, and write it to the CPU module.
Setting item
Setting
value
Setting detail
Buffer memory address
Axis 1
Axis 2
Axis 3
Axis 4
[Cd.13]
Positioning operation
speed override
200
Set the new speed in percentage (%).
1513
1613
1713
1813
200
V
t
Cd.13
[Y10]
[Y0]
[X0]
[X10]
[XC]
[X14]
[X8]
Positioning start signal
PLC READY signal
RD75 READY signal
Start complete signal
BUSY signal
Positioning complete
signal
Error detection signal
Positioning operation
speed override
Dwell time
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......