522
14 TROUBLESHOOTING
14.3 Error and Warning Details
Clearing errors or warnings
Eliminate the cause of an error or warning by referring to the actions described in the following, and clear the error or warning
using the error reset.
Page 523 List of Warning Codes
Clearing errors/warnings by each axis
By setting 1 to the following buffer memory address of [Cd.5] Axis error reset, the error or warning is cleared after the
completion of the processing below.
■
Processing
Error detection signal [X8, X9, XA, XB] is turned off.
[Md.23] Axis error No. is cleared.
[Md.24] Axis warning No. is cleared.
The value in [Md.26] Axis operation status changes from -1: Error to 0: Standby.
[Md.31] Status, Axis warning detection (b9) is turned off.
Clearing errors/warnings of all axes collectively
By setting 1 to [Cd.49] All axes error reset, errors or warnings of all axes are collectively cleared.
■
Processing
Error detection signal [X8, X9, XA, XB] is turned off.
[Md.23] Axis error No. is cleared.
[Md.24] Axis warning No. is cleared.
The value in [Md.26] Axis operation status changes from -1: Error to 0: Standby.
[Md.31] Status, Axis warning detection (b9) is turned off.
Axis No.
Buffer memory address ([Cd.5] Axis error reset)
1
1502
2
1602
3
1702
4
1802
Axis No.
Buffer memory address ([Cd.49] All axes error reset)
All axes
1933
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......