310
8 COMMON FUNCTIONS
8.6 History Monitor Function
8.6
History Monitor Function
This function monitors the start history, error history, and warning history stored in the buffer memory of RD75 during the
operation monitoring.
Start history
The start history of past 16 records of operations such as the positioning operation, JOG operation, and manual pulse
generator operation can be monitored. Once 16 records are stored, the oldest record is overwritten with the latest record.
Therefore, the latest 16 history records are stored at all times. This function allows users to check the operation sequence
(whether the operations have been started in a predetermined sequence) when the system is started.
The start history can be checked using the intelligent function module monitor window. The following describes the check
method.
1.
Display the "Intelligent Function Module Monitor" window.
[View]
[Docking Window]
[Intelligent Function Module Monitor]
[Intelligent Function Module Monitor 1] to
[Intelligent Function Module Monitor 10]
2.
Select the RD75 from the project view.
3.
Right-click
Select [Register to Intelligent Function Module Monitor] in the shortcut menu.
4.
Select the RD75 from the "Module List" in "Module Information Selection" window.
5.
In "Monitor Item Category List", select "Display by Axis Unit" or "Display by Item Unit", and click the [OK] button.
6.
Select [Online]
[Watch]
[Start Watching].
7.
In the registered "Intelligent Function Module Monitor" window, right-click "Start Completed", and select [Detailed Dialog]
in the shortcut menu. The start history is displayed.
The start history can be checked using the positioning monitor. For details on the positioning monitor, refer to the following.
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......