10 MONITORING/TEST
10.2 Positioning Test
■
OPR control
1.
Select a target axis to be tested from the pull-down menu of "Target Axis".
2.
Select "JOG/Manual Pulse Generator/OPR" from the pull-down menu of "Select Function".
3.
Select "Machine OPR" or "Fast OPR" from the pull-down menu of "OPR Method".
4.
Click the [OPR] button.
The on state of Near-point dog signal, Zero signal, and OPR complete flag can be checked on the monitor
part. Check the OPR completion on the monitor.