30
1 STARTING AND STOPPING
1.1 Starting
Procedure
The following figure shows the procedure for the multiple axes simultaneous start control.
Setting method
The following table lists the data settings to perform the multiple axes simultaneous start using Positioning start signal. (Set
the axis control data for the starting axis.)
For details on the settings, refer to the following.
Page 470 [Cd.3] Positioning start No.
Page 479 [Cd.30] Simultaneous starting axis start data No. (Axis 1 start data No.)
Page 479 [Cd.31] Simultaneous starting axis start data No. (Axis 2 start data No.)
Page 479 [Cd.32] Simultaneous starting axis start data No. (Axis 3 start data No.)
Page 479 [Cd.33] Simultaneous starting axis start data No. (axis 4 start data No.)
Setting item
Setting
value
Setting detail
Buffer memory address
Axis 1
Axis 2
Axis 3
Axis 4
[Cd.3]
Positioning start No.
9004
Set 9004, the start No. for the multiple axes
simultaneous start control.
1500
1600
1700
1800
[Cd.30]
Simultaneous starting axis start
data No. (axis 1 start data No.)
Set the simultaneous starting axis start data No.
Set 0 for the axis other than the simultaneous starting axis.
1540
1640
1740
1840
[Cd.31]
Simultaneous starting axis start
data No. (axis 2 start data No.)
1541
1641
1741
1841
[Cd.32]
Simultaneous starting axis start
data No. (axis 3 start data No.)
1542
1642
1742
1842
[Cd.33]
Simultaneous starting axis start
data No. (axis 4 start data No.)
1543
1643
1743
1843
Turn on Positioning start signal of the axis to be started.
Set Cd.30 to Cd.33 Simultaneous starting axis
start data No.
Write "9004" in Cd.3 Positioning start No.
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......