14 TROUBLESHOOTING
14.5 List of Error Codes
541
14
1A66H
Outside bias
speed range
A value outside the setting range is set in [Pr.7] Bias speed at
start of basic parameter 1.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1A67H
[Pr.7] Bias speed at start of basic parameter 1 is over [Pr.8]
Speed limit value.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Set values so that [Pr.7] Bias speed at start becomes equal to
or below [Pr.8] Speed limit value, and turn on PLC READY
signal [Y0].
For details, refer to the following.
Page 386 [Pr.7] Bias speed at start
Page 389 [Pr.8] Speed limit value
1A68H
Outside
electronic gear
selection
A value outside the setting range is set in [Pr.62] Electronic
gear selection of basic parameter 1.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1A69H
Outside speed
limit value range
A value outside the setting range is set in [Pr.8] Speed limit
value of basic parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 389 [Pr.8] Speed limit value.
1A6AH
The command pulse frequency converted from the value in
[Pr.8] Speed limit value of basic parameter 2 is over the
maximum output pulse of the module.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value so that the command pulse frequency is not
over the maximum output pulse of the module, and turn on
PLC READY signal [Y0] if the signal is off.
• RD75P: 200000 (pulse/s)
• RD75D: 5000000 (pulse/s)
1A6BH
Outside
acceleration
time 0 range
A value outside the setting range is set in [Pr.9] Acceleration
time 0 of basic parameter 2.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 390 [Pr.9] Acceleration time 0, [Pr.10] Deceleration
1A6CH
Outside
deceleration
time 0 range
A value outside the setting range is set in [Pr.10] Deceleration
time 0 of basic parameter 2.
[Operation of when the error has occurred]
■
At the start of operation
The operation is not performed.
■
During operation
The operation stops according to the setting of [Pr.39] Stop
group 3 sudden stop selection of detailed parameter 2
(deceleration stop/sudden stop). (for manual pulse generator
operation, deceleration stop only)
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 390 [Pr.9] Acceleration time 0, [Pr.10] Deceleration
1AA0H
Backlash
compensation
amount error
The number of pulses converted from the movement amount
per pulse is 256 or greater.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Set values so that the number of pulses converted from the
movement amount per pulse becomes smaller than 256, and
turn on PLC READY signal [Y0]. For details, refer to
391 [Pr.11] Backlash compensation amount.
1AA1H
Software stroke
limit upper limit
When the unit is degree, a value outside the setting range is
set in [Pr.12] Software stroke limit upper limit value of detailed
parameter 1.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
Software stroke limit upper limit value.
1AA2H
When the unit other than degree is set, [Pr.12] Software
stroke limit upper limit value is smaller than [Pr.13] Software
stroke limit lower limit value. (The error code: 1AA4H is stored
as well.)
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
When the unit is other than degree, set values so that [Pr.12]
Software stroke limit upper limit value becomes greater than
[Pr.13] Software stroke limit lower limit value, and turn on PLC
READY signal [Y0].
For details, refer to the following.
Page 392 [Pr.12] Software stroke limit upper limit value
Page 392 [Pr.13] Software stroke limit lower limit value
Error
code
Error name
Cause and description
Action
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......