14 TROUBLESHOOTING
14.5 List of Error Codes
545
14
1AC0H
Illegal sudden
stop
deceleration
time
A value outside the setting range is set in [Pr.36] Sudden stop
deceleration time of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 404 [Pr.36] Sudden stop deceleration time.
1AC1H
Stop group 1
sudden stop
selection error
A value outside the setting range is set in [Pr.37] Stop group 1
sudden stop selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 405 [Pr.37] to [Pr.39] Stop group 1 to 3 sudden stop
1AC2H
Stop group 2
sudden stop
selection error
A value outside the setting range is set in [Pr.38] Stop group 2
sudden stop selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 405 [Pr.37] to [Pr.39] Stop group 1 to 3 sudden stop
1AC3H
Stop group 3
sudden stop
selection error
A value outside the setting range is set in [Pr.39] Stop group 3
sudden stop selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 405 [Pr.37] to [Pr.39] Stop group 1 to 3 sudden stop
1AC4H
Outside
allowance
circular
interpolation
error width
A value outside the setting range is set in [Pr.41] Allowable
circular interpolation error width of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 407 [Pr.41] Allowable circular interpolation error
1AC5H
External
command
function
selection error
A value outside the setting range is set in [Pr.42] External
command function selection of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 408 [Pr.42] External command function selection.
1AC7H
Outside start
adjustment time
error
A value outside the setting range is set in [Pr.82] Start
adjustment time of detailed parameter 2.
[Operation of when the error has occurred]
■
At power-on or at turning on of PLC READY signal [Y0]
RD75 READY signal [X0] does not turn on.
■
At the start of operation
The operation is not performed.
Correct the value within the setting range and turn on PLC
READY signal [Y0] if the signal is off. For details, refer to
Page 408 [Pr.82] Start adjustment time.
1B00H
OPR method
error
A value outside the setting range is set in [Pr.43] OPR method
of OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B01H
OPR direction
error
A value outside the setting range is set in [Pr.44] OPR
direction of OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
1B02H
OP address
setting error
A value outside the setting range is set in [Pr.45] OP address
of OPR basic parameter.
[Operation of when the error has occurred]
RD75 READY signal [X0] does not turn on.
Correct the value within the setting range and turn on PLC
READY signal [Y0]. For details, refer to
Error
code
Error name
Cause and description
Action
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......