14 TROUBLESHOOTING
14.4 List of Warning Codes
525
14
0997H
Illegal external
command
function
A value outside the setting range is set in [Pr.42] External
command function selection of detailed parameter 2.
[Operation of when the warning has occurred]
Nothing changes in the operation even if External command
signal has been tuned on.
Correct the value within the setting range. For details, refer to
Page 408 [Pr.42] External command function selection.
0998H
Insufficient
movement
amount
Movement amount is not enough for automatic deceleration.
[Operation of when the warning has occurred]
The positioning stops immediately when the object has
reached the positioning address.
Set the address or movement amount necessary for the
deceleration to positioning data.
0999H
Illegal teaching
data No.
The positioning data No. outside the setting range is set.
[Operation of when the warning has occurred]
The teaching is not performed.
Set the positioning data No. within the setting range. For
details, refer to
Page 481 [Cd.39] Teaching positioning
099AH
Illegal teaching
data selection
The value outside the setting range is set in [Cd.38] Teaching
data selection.
[Operation of when the warning has occurred]
The teaching is not performed.
Correct the value within the setting range. For details, refer to
Page 481 [Cd.38] Teaching data selection.
099BH
Target position
change not
possible
The target position change has been requested while the
control other than ABS1 and INC1 in [Da.2] Control method is
being executed.
[Operation of when the warning has occurred]
The target position is not changed.
Do not turn on Target position change request flag while the
control other than ABS1 and INC1 in [Da.2] Control method is
being executed.
099CH
Target position change request flag has been turned on in
continuous path control.
[Operation of when the warning has occurred]
The target position is not changed.
Do not turn on Target position change request flag when
Continuous path control is set.
099DH
The target position change has been requested while the
operation is decelerating to a stop.
[Operation of when the warning has occurred]
The target position is not changed.
Do not turn on Target position change request flag during
deceleration stop.
099EH
The target position change has been requested when Speed
change 0 flag ([Md.31] Status: b10) is on.
[Operation of when the warning has occurred]
The target position is not changed.
Do not turn on Target position change request flag when
Speed change 0 flag ([Md.31] Status: b10) is on.
099FH
The value set in [Cd.27] Target position change value (new
address) is outside the software stroke limit range (+).
[Operation of when the warning has occurred]
The target position is not changed.
Correct the value in [Cd.27] Target position change value
(new address) if it is outside the software stroke limit range
(+). For details, refer to
Page 478 [Cd.27] Target position
09A0H
The value set in [Cd.27] Target position change value (new
address) is outside the software stroke limit range (-).
[Operation of when the warning has occurred]
The target position is not changed.
Correct the value in [Cd.27] Target position change value
(new address) if it is outside the software stroke limit range (-).
For details, refer to
Page 478 [Cd.27] Target position
09A1H
When the unit is degree, the value other than 0 to 359.99999
is set in [Cd.27] Target position change value (new address).
[Operation of when the warning has occurred]
The target position is not changed.
Correct the value of [Cd.27] Target position change value
(new address) within the setting range. For details, refer to
Page 478 [Cd.27] Target position change value (new
09A2H
Pre-analysis
incomplete
start
A positioning start trigger has been input before 1: Analysis
completed is stored in [Md.61] Analysis complete flag.
[Operation of when the warning has occurred]
A pulse output starts once positioning data analysis is
completed and 1: Analysis completed is stored in [Md.61]
Analysis complete flag.
Start positioning after 1: Analysis completed is stored in
[Md.61] Analysis complete flag.
09A4H
Manual control
start in pre-
analysis mode
The manual control is started in pre-analysis mode.
[Operation of when the warning has occurred]
The manual control does not start.
Perform the manual control after 0: Normal analysis mode is
set in [Cd.43] Analysis mode setting.
09A6H
Step start
disabled
1: Step continue has been set in [Cd.36] Step start request in
pre-analysis mode.
[Operation of when the warning has occurred]
The step does not start.
Do not set 1: Step continue in [Cd.36] Step start request in
pre-analysis mode.
Positioning data analysis has been performed after 1: Carry
out step operation was set in [Cd.35] Step valid flag.
[Operation of when the warning has occurred]
The step operation is not performed.
Do not set 1: Carry out step operation in [Cd.35] Step valid
flag.
Warning
code
Warning
name
Cause and description
Action
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......