12 DATA USED FOR POSITIONING CONTROL
12.3 Basic Setting
[Pr.42] External command function selection
Select a function with which external command signals are associated.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Default value
The default value is 0: Start with external command for all the axes.
To enable the external command signal, [Cd.8] External command valid must be set to 1.
[Pr.82] Start adjustment time
Set the amount of time from when a positioning start trigger signal is input to when the RD75 starts outputting pulses in units
of ms with Quick start function. The actual time elapsed before a pulse output starts depends on the start trigger.
• Start with an external command signal: 20
s + [Pr.82] Start adjustment time
• Start with a positioning start signal: 8
s + [Pr.82] Start adjustment time
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Setting range
The following table shows the setting range.
■
Default value
The default value is 0 for all the axes.
External command function
selection
Setting
value
Description
Start with external command
0
Starts a positioning operation by inputting an external command signal.
External speed change request
1
Changes the speed in the current positioning operation by inputting an external command signal. Set a
new speed value in [Cd.14] New speed value.
Speed-position/position-speed
switching request
2
Switches the control from the speed control to the position control in the speed-position switching control,
or from the position control to the speed control in the position-speed switching control by inputting an
external command signal. To enable speed-position switching, set [Cd.24] Speed-position switching
enable flag to 1. To enable position-speed switching, set [Cd.26] Position-speed switching enable flag to
1.
Skip request
3
Skips the current positioning operation by inputting an external command signal.
Buffer memory name
Axis 1
Axis 2
Axis 3
Axis 4
[Pr.42] External command function selection
62
212
362
512
Buffer memory name
Axis 1
Axis 2
Axis 3
Axis 4
[Pr.82] Start adjustment time
134
284
434
584
135
285
435
585
Setting value with engineering tools
Setting value with programs
0.00 to 10000.00 (ms)
0 to 1000000 (
10
-2
ms)
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......