17. Checking and Clearing of Settings
17.1 Parameter clear / All parameter clear
17
Checking and Clearing of Settings
17.1
Parameter clear / All parameter clear
• Set "1" to
Pr.CL Parameter clear or ALLC All parameter clear
to initialize the parameter. (The parameter cannot be cleared
when
Pr.77 Parameter write selection
= "1".)
• Pr.CL does not clear calibration parameters or the terminal function selection parameters.
• Refer to the parameter list on
for parameters cleared with this operation.
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press the PU/EXT key to choose the PU operation mode. The PU LED turns ON.
3.
Selecting the parameter setting mode
Press the MODE key to choose the parameter setting mode. (The parameter number read previously appears.)
4.
Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "Pr.CL" appears for Parameter clear or "ALLC" for All
parameter clear, and press the SET key. "0" (initial value) appears.
5.
Parameter clear
Turn the setting dial or press the UP/DOWN key to change the value to "1". Press the SET key to confirm the setting.
"1" and "Pr.CL" ("ALLC") are displayed alternately after parameters are cleared.
NOTE
• "1" and "Er4" are displayed alternately when the operation mode is other than the PU operation mode.
• Stop the inverter first. Writing error occurs if parameter clear is attempted while the inverter is running.
• To clear the parameter, the inverter must be in the PU operation mode even if "2" is set to
Pr.77
.
• For availability of the Parameter clear or All parameter clear operation for each parameter, refer to the parameter list on
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to show the setting again.
• Press the SET key twice to show the next parameter.
Setting
Description
Pr.CL Parameter clear
ALLC All parameter clear
0
Initial display (Parameters are not cleared.)
1
The settings of parameters except for calibration parameters
and terminal function selection parameters are initialized.
The settings of all the parameters, including calibration
parameters and terminal function selection parameters, are
initialized.
1) Press the PU/EXT key.
The PU LED turns ON, and "1" appears on the monitor. (When
Pr.79
="0" (initial value))
2) Press the SET key to clear the parameter.
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...